PARAMETER IDENTIFICATION FOR THE CONTROL OF THERMAL COMFORT Konstantyn Spasokukotskiy

Ralf Grassnick

Universität der Bundeswehr München, Institute for Measurement and Automation Technology Werner-Heisenberg-Weg 39 D-85577 Neubiberg Germany

Universität der Bundeswehr München, Institute for Measurement and Automation Technology Werner-Heisenberg-Weg 39 D-85577 Neubiberg Germany

Michael Horn Prof. Dr-Ing. Universität der Bundeswehr München, Institute for Measurement and Automation Technology Werner-Heisenberg-Weg 39 D-85577 Neubiberg Germany

KEYWORDS Parameter identification, Indoor climate control, Thermal comfort, Room model, Controller parameter

ABSTRACT The demand-adjusted control of thermal comfort in buildings is a step ahead in comparison with the indoor temperature control. It allows HVAC (Heating Ventilation and Air-Conditioning) systems working in compliance with real heating and ventilation demands, e.g. presence depended heating. The latter contains great potential to reduce the energy consumption of heating facilities in comparison with standard steady-state approaches. The online parameter identification of residential buildings for an automated demand-adjusted decentralized indoor climate control is proposed. The basic parameter for the realisation of such a control system is the objective thermal comfort. A special physical model is used, in order to analyse the dynamic thermal properties of a given room. This includes the estimation of non-measurable physical values at any point in space and time in the room. The model properties are the basis of a correct parameterisation of the controller. The system functions are generated for any desired operating point of the control system. Thus the controller parameters can be adapted to any of these operating points, in order to increase the thermal comfort and to decrease the energy consumption.

INTRODUCTION Strategies to reduce and optimise energy consumption are a global challenge, both economically and environmentally. Investigations show, that a large part of total energy consumption is used for residential buildings (Fig.1a). This consumption consists mainly of energy required for heating. Thus a simple optimisation of the heating energy consumption could have more potential of energy saving than a big progress in other branches.

- 219 -

Potential of energy saving %

B C

D 0

Reduction of temperature to C

A)

A inhabitants presence dependent heating a n d v e n ti la tio n w i th h e a t re c u p e ra t io n for a Family apartment B inhabitants presence dependent heating and ventilation for a Family apartment C inhabitants presence dependent ventilation for a Family apartment D inhabitants presence dependent heating for a Family apartment B)

FIG. 1 - A) ENERGY CONSUMPTION IN GERMANY (DATA IN ACCORDANCE WITH [7, 8]) AND B) POTENTIAL OF HEATING ENERGY SAVING IN PRIVAT BUILDINGS Beginning in the early 70’s, in many countries a number of attempts to force the reduction of energy consumption in the private sector has been launched. For example in Germany four legislative papers were issued in 1976, 1982, 1994, and 2001 [1, 2]. New construction techniques and insulating materials have been developed which remarkably reduce the heat losses of buildings, enabling high energy savings at the cost of a diminished natural air and heat exchange. In this situation, appropriate heating and ventilation of the rooms must guarantee sufficient indoor air quality [3, 4]. Improvements of HVAC systems in residential buildings aim at a reduction of energy consumption and an adjustment of comfortable climate in rooms. To meet these demands, decentralized automated thermal climate control, in the sense of demand-adjusted heating and ventilation separately for each room, offers great technical possibilities (Fig. 1b) [5, 6, 7, w1]. The demand for heating and ventilation can be defined according to the control value in the time or/and amplitude domain, i.e. inhabitant’s presence dependent or/and activity dependent. In both cases the HVAC system should allow dynamical action with bigger state deviation in comparison to conventional systems. Hence, in order to provide optimal regulation, the control algorithm should gather data about the room’s behaviour. The core of a demand-controlled system must be therefore a thermodynamic model of the room. Large number of models has been developed in recent decades (e.g. [9, 10, 11]). Unfortunately, sophisticated models are either too complex for on-line control devices or need huge sets of experimental data to manipulate with.

- 220 -

Simplified models are adjusted to a specific task and cannot be used with new terms of reference. Furthermore, with known models it appears to be impossible to use the control system in critical states, like asymmetric radiation, distributed thermal load, etc.. Therefore, a novel approach to the thermodynamic model adapted to the needs of a demand-adjusted room climate control is proposed. In this sequel, the technique of room modelling for controller needs will be presented and an example for a real-world realisation will be discussed.

CONTROL CONDITIONS AND THERMAL COMFORT The sole criterion to develop any climate control device is the improvement of thermal comfort [12]. The theoretical and practical foundations for subjective thermal comfort in residential buildings are described in an international norm [13]. The analysis of important parameters influencing thermal comfort is leading to the conclusion that the set of physical parameters commonly taken into account by climate control systems is of limited use to the discussed problem of demand-adjusted control [14]. TABLE 1 - DIFFERENCES IN TYPICAL PARAMETER SETS FOR ROOM THERMAL CONTROL (IN ACCORDANCE WITH [5, 13, 15, 16, 17]) N

COMFORT PARAMETER

CONVENTIONAL

DEMAND-CONTROLLED

HVAC SYSTEM

HVAC SYSTEM

1

Air temperature

Very important

Very important

2

Air velocity

Not important

Important

3

Air humidity

Not important

Important

4

Metabolic rate

Neglected

Very important

6

Clothing

Neglected

Very important

5

Radiation temperature (distribution of

Neglected

Important

Neglected

Neglected

wall temperature) 7

Mechanical work

This is easy to understand if one typical example of presence-demanded heating is considered (presence – heating; absence – no heating). The walls have a slower dynamic behaviour in comparison with air in the room. Because usually the air temperature in a room is nearly stable, the wall temperature changes can be neglected and the wall temperatures are set to a constant value depending on the measured mean air temperature. Contrary to conventional control systems, the proposed approach allows large dynamic bands of environmental physical parameters. Because the air- and the wall temperature are “independent” parameters, due to different dynamic by spontaneous state changing, the changing of the wall temperature should not be ignored, and hence for any room state the comfort state can be adjusted.

- 221 -

In Table 1, results of parameter analysis for the modern room climate control and differences in comparison with earlier control realizations [5, 15] are shown. All following examples are based on measurements and calculations for the ‘office room’ (Room 0103) of the Smart-HOME Research Lab on the University campus (Fig. 2).

The part for experiments

FIG. 2 - A) SMART HOME LAB AT THE BUNDESWEHR UNIVERSITY MUNICH – GENERAL VIEW AND B) LOCATION OF TEST ROOMS [W3]. in livin g ro o m

T yp ical states fo r th erm al en viro n m en t: in b ath ro o m b y in ten sive h eatin g w ith v en tilato rs

FIG. 3 - CALCULATED SAMPLES OF PMV CHANGING SUBJECT TO DIFFERENT PARAMETER CHANGINGS FOR THE OFFICE ROOM (0103) IN THE RESEARCH LAB The dependency of a significant comfort factor, the Predicted Mean Vote (PMV) [16], on the changing of room parameters is calculated for two cases:

- 222 -

 Transient room state by air heating (i.e. ideal heating by ventilation devices),  Transient room state by radiation heating (i.e. ideal heating by radiation panels). “Transient” means, that the room conditions by heating of a cool room are taken into account. That is when values of important physical parameters have in a shortest time the largest deviation from the appropriate steady-state. Some typical examples of comfort factor dependencies are shown in Fig. 3. They are used in order to demonstrate the sensitivity of human thermal perception influenced by different physical values for demand-controlled heating and ventilation systems. The comfort surface was obtained in 3D i.e. as a function of 2 parameters - mean wall temperature and air temperature (here they are given as deviations from the normal values 21°C and 19.5°C accordingly). The third parameter changing in Fig. 3 is given as the additional set of 2 projections for described comfort function in 3D domain. For both discussed heating cases, the influences of same physical parameters (here clothing, air velocity, etc.) on the PMV factor are nearly similar and for control aims could be assumed identical.

OBTAINING OF CONTROL PARAMETERS One problem is, that a lot of control parameters (Table 1), which are needed for a new approach, cannot be measured easily. Furthermore, for a comfort-driven climate control, the establishment of nearly all airconditioning parameters at the person’s localization in the room and parameters such as type of clothes etc. have to be known. Hence, the extended set of control parameters defines an additional task for the measurement environment or/and for the thermodynamic modelling. The second problem is a practical implementation of a controller that allows the correct work with the extended set of control parameters. The proposed technique uses an extended thermodynamic model as an observer and as a base for many sets of simple room models (like Proportional Timedelay (PT) characteristics or similar) for certain operating states. Such dual model structure is useful for maintenance of cheap and standard heating and ventilation controllers. The desired changing of controller properties is realised due to on-line changing of controller parameters. MODELLING OF DYNAMIC STATE CHANGES Steady-state conditions cannot be assumed for demand-controlled rooms. The most effective energysaving mode is presence dependent heating and ventilation. This is leads to heating pauses and dynamic state changes as discussed in the example on page 3. The circumstances, caused by the comprehensive definition of the thermal comfort in controlled rooms and the needs in dynamic objectiveness of the thermal model, define the following model and controller requirements:  detailed consideration of a large number of physical phenomena,  simultaneous consideration of a large variety of physical parameters in the controlled room,  simplicity for on-line processing,  easy configuration for easy handling in large-scale production. The complex thermodynamic model is based on a modified Glück-model [18]. The original structure of the model consists of a geometric room model with multi-sectioned wall surface and multi–zoned air

- 223 -

Radiation processor

Processor for distributed heating devices

Technical data: Airflow to the room, temperature of the air, positions of air jets, positions and power of electrical and heating devices, etc.

Personal data: Number, activity, clothing and positions of presented in room persons

Environmental data: Air temperature in neighbor rooms, geometrical room description, wall description, position of doors and windows,etc.

Weather data: Air temperature, air humidity, air velocity, wind direction, direct and diffuse solar radiation

INPUTS

volume inside a room with mechanisms of convective, radiative and conductive heat transfers. Furniture geometry can be co-defined and points of internal heat sources with radiative and convective character could be integrated. The solving method is a mixture of Finite Difference Method (FDM) and empirical equations. It gives to the model a precision of Computational Fluid Dynamic (CFD) and a short calculation time of special physical contributions. Thus in comparison with other known models in public domain it has the best (calculation time)/(features) coefficient [w2].

Thermal comfort

Distribution of wal temperatures, etc

Distribution of ai velocity in the room

Distribution o asymmetric radiation in the room

Distribution o comfort factor (PMV) in the room

Distribution of ai temperature in the room

OUTPUTS

ROOM MODEL

FIG. 4 - STRUCTURE OF INPUT AND OUTPUT DATA FOR THE MODIFIED GLÜCKMODEL

A)

B)

FIG. 5 - A) CALCULATED AIR TEMPERATURE

B) CALCULATED AND MEASURED AIR

TEMPERATURES, WALL TEMPERATURES AND PMV VALUES

- 224 -

Structures for object oriented manipulation of typical furniture elements, inhabitants, lighting, radiators etc. have been developed additionally. As important facts, the inclusion of the influence of solar radiation on the heat transfer coefficients of the wall elements and the solar energy flow inside the room, as well as mechanisms of energy transmission outwards, have been added. Furthermore, a user-friendly interface and a block structure, adapted for automation, have been realized in a LabVIEW environment. The modified Glück-model (Fig. 4) allows estimating the thermodynamic state of the system at any position in the room (Fig. 5). The calculation time depends on the accuracy of the result. The implementation of similar algorithms in other programming environments (i.e. C++) could reduce the computation time to a twentieth. MODELLING OF STANDARD FUNCTIONS The dilemma of the contradiction of simplicity and easy configuration on the one hand and a complex non-linear description of the energy distribution in the room with a lot of significant variables and parameters on the other hand is an important problem of new control approaches. The requirement for simplicity and easy configuration is usually met in control engineering by the classical linear approach (P, I, PI, PID, PTn controllers) [19, 20]. In order to realise control systems with linear object description, a large number of dependencies should be designated. The scheme of an Many Input – Many Output Linear Timeinvariant System (MIMO LTI)-system appears in Fig. 6.

G32

G31

G22

X3

G21

G12

X2

G11

X1

1 N

2

+

+ Y1

Y2

FIG. 6 - GENERAL STRUCTURE OF LINEAR MODELS FOR CONTROL AIMS: Xa –INPUT; Yb – OUTPUT; Gab – LINEAR PROCESS CHAINS; 1, 2,…, N – PARAMETER SETS FOR DIFFERENT CONTROL CONDITIONS There are two problems to get linearity for physical descriptions: The experiment time needed and the impossibility to carry out “clean” experiments for identification of independent linear functions with experimental methods. In best case, the time t for experiments with the process chain can be approximated: t = K X ⋅ KY ⋅ N ⋅ (τ max ⋅ ς ) ,

(1)

- 225 -

where Kx and Ky are the numbers of inputs and outputs respectively, N is the number of linear state dependencies for a non-linear system, τmax is the maximal time constant of the system, and ξ is a coefficient for independent measurement attempts (e.g., ξ takes into account the cooling time after the heating experiment etc.). In most practical cases it is to assume ξ > 2. The time constants of buildings are normally big (ca. n*10 hours). According to eq. (1), a system identification of a system with 10 inputs, 1 output, and a time constant of 20 hours with a 3-point linear approach would take at least 2 months. To obtain the Gab-dependence (Fig. 6) without disturbances, all variables and parameters except Xa and Yb have to be “frozen”. This is impossible on a real world complex object like a building with numerous inter-dependencies and mutual disturbances. Again, there is no way out without a comprehensive thermal building modelling.

Priory information about function structure

Mechanism of subdomain identification

Curve fitting

(Convolution)

Determining of Jump response function

(Deconvolution)

Determining of impulse response function

Complex thermodyna mic model of building

Pattern fun ction generator

GUI Input/output System description

Freeze block

Measured or prior calculated, generated data

(0 position -current state position)

The proposed modelling technique consists of two parts. First of all, there is the complex model with a minimum set of equations (see pg.6). It is given by physical phenomena and variables, which are important for the problem. But the model is still non-linear. The second part in the modelling process is an automatic mechanism for identification of LTI system functions at given operating points (Fig. 7). In all cases, the calculation time for such applications should be relative short, in order to allow finite time pre-processing operation. The critical component here is again the complex thermodynamic model of the building.

Output select

start

“State” Coefficients (Simplified functionality for actual system state)

Signal: state changing will be supposed or identified

FIG. 7 - SYSTEM IDENTIFICATION ALGORITHM There are three possibilities of identification in applications with a dual model structure as described above: 1. Off-line: The user measures the required data in front of the identification process. This data will be used for the validation of user-inputs and as input parameters of the model. After that, typical state conditions will be simulated and control parameter sets will be calculated (Fig. 8a).

- 226 -

2. On-line: A number of simultaneous calculations - one for each functionality - to compute the model set for the current system operating state point have to be executed on a powerful computation platform (Fig. 8b). 3. Hybrid: At system start a powerful computation platform is installed, which executes on-line calculations for real-world conditions. Afterwards, the parameter sets will be redefined and new parameter sets will be stored in a cheap control device (Fig. 8c). A

Mechanism of subdomain identification

B

C Measured or prior calculated, generated data

Mechanism of subdomain identification

Measured data

Predefined typical states

start

Signal: next loop

“State” Coefficients

Actual typical states

start

Actual state

Signal: state changing will be supposed. Date base with appropriate state coefficients is not present or actual.

Actual “State” Coefficients

Main Controller

Mechanism of subdomain identification

Main Controller

“State” Coefficients

Main Controller

FIG. 8 - IDENTIFICATION OF SYSTEMS WITH DUAL MODEL STRUCTURE. A) OFF-LINE, B) ON-LINE IDENTIFICATION AND C) HYBRID TYPE. For the Smart HOME Laboratory the functions of heating response have been represented as functions with PT3-characteristic. The coefficients of these functions are automatically obtained using the Levenberg-Marquardt algorithm as shown in Fig. 6. Functional dependencies have been received for heating power, power of electrical devices in the room, number of occupants in the room, sunshine, etc. as causes and air temperature in the room at different positions as well as with PMV factor as effects. Table 2 shows some data sets. TABLE 2 - SAMPLES OF CALCULATED COEFFICIENTS FOR OFFICE ROOM N

DEPENDENCE

1

Heating power -Air temperature

2

Heating power - PMV

K

T1

T2

T3

0,07

797

1045

994

0,0061

1497,9

1495,2

1495,8

Calculation speed under a LabVIEW environment is about 20-40 minutes on a PC, that allows today offline or hybrid type system identification. For this purpose an embedded PC can be used as a controller.

CONTROLLER DESIGN

- 227 -

A great number of control approaches provide the indoor air temperature as the only important environmental variable. In doing so P, PI [21], Fuzzy [22] or predictive [23] controllers have been used. Some more extensive approaches include the presence of persons [24] or the indirect involvement of comfort using representative measurable values [5]. Regarding the PMV as controlled variable, the room is a time-variant system with distributed parameters. But as mentioned above, it is possible to describe this system by PT3 transfer functions. Different time constants determine different behaviour on selected operating points. The disturbances in the system are deterministic as well as stochastic signals. A parameter optimised controller has been chosen, which will be adapted to the respective operating point via adjustment rules and which enables the control with both types of disturbance signals. A controller of this class is a PID controller. In consideration of the disturbances, two control strategies have been tested. The first is shown in Fig. 9a. It is a feed forward PID control. The manipulated variable u is influenced by an additional open loop control Gs subject to the disturbances z. The second control strategy is an adaptive PID controller as shown in Fig. 9b. The adaptation of the controller parameters is oriented on the time variation of the error variable e and the disturbances z. The parameter settings for the PID-controllers are based on case scenarios (bedroom, bathroom, living room, kitchen at night and day respectively as well as heating, cooling and air conditioner maintenance, etc.)

A)

B)

FIG. 9 A) FEED FORWARD AND B) ADAPTIVE CONTROL CIRCUIT

CONCLUSIONS A simplified mixed type physical thermodynamic modelling technique has been discussed. It has been developed for specific tasks of demand-adjusted decentralised room climate control. The applied analysis of the task demand-adjusted decentralised room climate controls is discussed too. The complex model is a substitution of the real process. It has been optimised for the sprcific control demands such as on-line calculation and precise dynamic. Using this model and modelling technique, parameters for an LTI system, that represents the real process on desired operational points, have been obtained. Thus it is possible to adapt controller parameters to any desired operational point. The modelling technique has been tested in real-world experiments.

- 228 -

As a result, an energy saving up to values in Fig. 1b will be expected. Simultaneously to an energetic contribution with this new approach it is possible to provide better thermal comfort in all types of buildings.

ACKNOWLEDGEMENTS This work is supported by the Bayerische Forschungsstiftung under Grant 283/98 (Intelligent Instrumentation of Homes, IWO-BAY).

REFERENCES [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]

[11] [12] [13] [14] [15]

"Verordnung über einen energiesparenden Wärmeschutz bei Gebäuden (Wärmeschutzverordnung)", August, 1994, (in German) "Energieeinsparverordnung /Änderungen die der Bundesrat empfohlen hat" (Bundesrat Drucksache 194/1/01, vom 4. Juli 2001), (in German) Jelondz, D., Spasokukotskiy, Ruser; "Concept and realization of an EIB-based automated room climate control"; Muenchen, EIB Scientific Conference, 2001. Eisenmann, G.; “Ist das Heizsystem im künftigen Niedrigenergiehaus problematisch?”, Bauphysik 20 (1998) H4,p.115-121, (in German) Bernard, Th., Kuntze, H.-B.: "Sensor-Based Management of Energy and Thermal Comfort. in: Sensors in Intelligent Buildings", Wiley-VCH, Weinheim 2001. Voss, K.: "Experimintelle und theoretische Analyse des thermischen Gebäudeverhaltens für das energieautarke Solarhaus Freiburg“, Fraunhofer IRB Verlag, 1997, (in German) "Energieeinsparung für Gebäude : Stand der Technik"; Entwicklungstendenzen / Heinz Eickenhorst / Lajos Joos (Hrsg.).-Essen : Vulkan-Verl., 1998, (in German) Endenergieverbrauch in Deutschland 1999 / Verband der Elektrizitätswirtschaft – VDEW – e.V. – Frankfurt am Main, 2000, (in German) Haghighat, F.: "Determination of transient heat conduction through building envelopes – a review", BIBINF USA, ACHRAE transactions, Vol.98, pt.1, 1992. Udagava, “Development of a simulation program for heat loads and room temperatures of a residential building”, 4th International Symposium on the use of computers for environmental engineering related to buildings, Tokyo, April 1983, p.207-212 Andersen K., K., Madsen, H., Hansen, L.: "Modeling the heat dynamics of a building using stochastic differential equations", Energy and Buildings 31 (2000), p.13-14 Fanger, P.O. ; Thermal comfort; New York, McGraw-Hill Book Company,1972 DIN ISO 7730, “Moderate thermal environments – Determination of the PMV and PPD indices and specification of the conditions for thermal comfort”, 1994. Schratt, L., Horn, M., Tränkler, H.-R.: "Decentralized, demand controlled heating und ventilation in the research project IWO-BAY", EXPO 2000, Hannover, 2000. Mayer, E., Schwab, R.; "Bewährt sich die nene Klimasummengröße Äquivalenttemperatur bei der Beurteilung des Innenraumklimas?“, Bauphysik 20 (1998) H6, p.261-266, (in German)

- 229 -

[16] Thermal comfort. ASHRAE Handbook - Fundamentals, 1997 [17] Deque, O., et al.: "Grey boxes used to represent buildings with a minimum number of geometric and thermal parameters"; Energy and buildings 31 (2000) p.29-35. [18] Glück, B.: Wärmetechnisches Raummodell; Heidelberg: Müller, 1997, (in German) [19] Stanley, M., Shinners: Advanced Modern Control System Theory and Design; Wiley, John & Sons Incorporated. 1998. [20] Schmidt G.: Basics of control technic; Berlin, NewYork, London, Paris: Springer, 1991. [21] Kremonke A.: "Energetischer Einfluß raumseitiger Anlagenparameter. Bewertung von kostengünstigen anlagentechnischen Energiesparmaßnahmen im Gebäudebestand, Abschlußbericht". TU Dresden: Unipublikation 1999. (in German) [22] Haissig C.: "Adaptive Fuzzy Temperature Control for Hydronic Heating Systems". Proceedings of the 1999 IEEE International Conference on Control Applications. Hawai’i, USA, 1999. [23] Lute P., v.Paassen D.: "Optimal Indoor Temperature Control Using a Predictor". IEEE Control Systems. 1995. [24] Mozer, M.C. et al.: "The Neurothermostat, Predictive Optimal Control of Residental Heating Systems". Advances in Neural Information Processing Systems 9. Cambridge, MA: MIT Press. 1997.

LINKS [w1] http://www.ier.uni-stuttgart.de/public/abt/ren/ho_err.htm, "Bedarfsgerechte Einzelraumheizungsregelung“, 2001, (in German) [w2] http://www.esru.strath.ac.uk/courseware/Class-mod+sim/sim_theory.htm, “Modelling and simulation for environmental engineering”, 2001. [w3] http://smarthome.unibw-muenchen.de, “Virtual Tour, Intelligent Home”, 2001. [w4] http://www.dulley.com/ref/fe019.htm,” Energy Efficient Lighting”, 2001.

- 230 -

Parameter identification for the control of thermal comfort

ABSTRACT. The demand-adjusted control of thermal comfort in buildings is a step ahead in comparison with the indoor temperature control. It allows HVAC (Heating Ventilation and Air-Conditioning) systems working in compliance with real heating and ventilation demands, e.g. presence depended heating. The.

536KB Sizes 0 Downloads 212 Views

Recommend Documents

Impact of Building Architecture on Indoor Thermal Comfort Level: A ...
Thermal (LMT) model was used to evaluate the net heat gain to the building ... to derive the human sensational scale using Predictive Mean Vote (PMV) index,.

Knowledge-based parameter identification of TSK fuzzy ...
Available online 3 September 2009. Keywords: ... identification of consequent parameters in order to have a good .... signifies the degree of closeness of the rth rule center to the center ..... quadratic programming to obtain optimal values of mr.

Knowledge-based parameter identification of TSK fuzzy ...
nonlinear input to output mapping is achieved by quantifying a domain expert's ... form that makes the identification of TSK models from historical process data far ... define the characteristics of these fuzzy sets such as their shapes and spread.

an adaptive parameter control strategy for aco - Semantic Scholar
Aug 16, 2006 - 1College of Computer Science and Engineering, South China University of Technology, Guangzhou, P. R. ... one of the best performing algorithms for NP-hard problems ..... program tools, systems and computing machines.

Parameter control in evolutionary algorithms ...
R. Hinterding is with the Department of Computer and Mathematical. Sciences, Victoria .... of parameters to optimize the on-line (off-line) performance of. 2 By “control ..... real-valued vectors, just as modern evolutionary programming. (EP) [11] 

Parameter control in evolutionary algorithms
in recent years. ... Cooperation Research in Information Technology (CRIT-2): Evolutionary ..... implies a larger degree of freedom for adapting the search.

Identification of a best thermal formula and model for oil ...
Identification of a best thermal formula and model for oil and winding ... new model with the good best fit for the heat transfer ..... degrees from KTH University,.

parameter estimation for the equation of the ...
School of Electrical and Computer Engineering, Electric Power Department,. High Voltage Laboratory, National Technical University of Athens, Greece. ABSTRACT. This paper presents the parameter estimation of equations that describe the current during

Identification of a best thermal formula and model for oil ...
new model with the good best fit for the heat transfer ... Index: best fit, simulation, identification, error, model. 1. ... Cc: thermal capacitance core and winding.

Parameter evaluation for the equation of the ...
It has been observed [8] that using the circuit defined in the. Standard and for .... t1 (ns). 37.17. 36.64. 87.50 t2 (ns). 22.53. 21.68. 0.20. Fg. 31.86. 31.93. 59.50.

Dong et al, Thermal Process System Identification Using Particle ...
Dong et al, Thermal Process System Identification Using Particle Swarm Optimization.pdf. Dong et al, Thermal Process System Identification Using Particle ...

Model Predictive Control of Thermal Energy Storage in ... - Berkeley
Abstract—A preliminary study on the control of thermal energy storage in building cooling systems is presented. We focus on buildings equipped with a water ...

Model Predictive Control of Thermal Energy Storage in ...
and demonstration of energy-efficient technologies and prac- tices. It consists of a ... distribution system and secondary distribution loops serving each building of the ..... charge for the service under Schedule E-20 is the sum of a customer ...

Model Predictive Control of Thermal Energy Storage in ... - CiteSeerX
and cooling systems, their enhanced efficiency depends on ... can be applied to a wider class of buildings systems which ... accounting for pump power.

Parameter Determination of Heidler's Equation for the ...
waveform and its parameters, but it doesn't define an equation for the ESD current. ... gives the best fitting curve to the experimental data. 1 INTRODUCTION ... electronic equipment towards ESD is tested according to the IEC 61000-4-2 ...

Control and Identification of DC Machine by Neural ...
main advantages of DC motors are easy speed or position ... to offer advantages over classical feedback control methods ..... Solar Energy Journal, Vol. 76, 2004 ...

Identification and Control of Nonlinear Systems Using ...
parsimonious modeling and model-based control of nonlinear systems. 1. ...... In this example, the flow rate is constant ... A schematic diagram of the process. Vh.

Apparatus for controlling thermal dosing in a thermal treatment system
Sep 8, 2005 - Patent Documents. Reissue of: (64) Patent No.: 6,618,620. Issued: Sep. 9, 2003. Appl. No.: 09/724,670. Filed: Nov. 28, 2000. (51) Int. Cl. A61B 18/04 .... 9/2007 Talish et 31, system for ultrasound surgery,” IEEE Trans. Ultrason. Ferr

Outsourcing of Accounting Function for Unique Identification ...
Outsourcing of Accounting Function for Unique Identification Authority of India..pdf. Outsourcing of Accounting Function for Unique Identification Authority of ...

Too Close for Comfort
tered the consumer lexicon, making Web surfers reluctant to give up information .... The Web hosting site's registration page then contained the statement, “We ...

The non-symmetric Nitsche method for the parameter-free imposition ...
Jun 23, 2016 - Immersed domain finite element methods approximate the solution of ... free weak enforcement of boundary and interface conditions in ...... 100. ( # elements ). 1/2. Rel. error in L. 2 norm. Conservative flux (global stab.).

Genetic Programming for the Identification of Nonlinear ...
The data-driven identification of these models involves ... Most data-driven identification algorithms assume .... With the use of this definition, all of the linear-in-.

Supervised fuzzy clustering for the identification of fuzzy ...
A supervised clustering algorithm has been worked out for the identification of this fuzzy model. ..... The original database contains 699 instances however 16 of ...