Control unit for isolated operation gensets KEA 102 INSL General The automatic control unit KEA 102 INSL is used for gensets in isolated operation. Complete generator protection is included. The additional relay unit RZ 071-D of the KEA 070 series is included in the delivery. The output relay function and the parameters can be set with a PC. As the KEA 102 is the same size and is attached in the same manner as its predecessors, it can be exchanged without difficulty. The automatic control unit is simple to operate as it is operated by using the keys on the control panel.

Functions

• Start-stop for Diesel and gas engine with checking of preliminary start-up conditions • Sensors for generator voltage, frequency and rotating field (asymmetry) • Generator current sensor: Overload, short-circuit, unbalanced load and thermal overload (bimetal relay) • 48 alarm signals, of which 19 alarms with programmable text and actuation, 7 alarms (alarms 24-26 and 33-36) with programmable actuation • Software for sprinkler operation • For each analogue signal input, actuation of two alarms via limits • Two potential-free analogue signal outputs, e.g. for direct actuation of speed controllers or other controllers • Parameters can be set by using the keys and the display or via a fibre optics or USB interface with the ParaWin software • Data transfer to a central control system via a CAN bus interface • CAN bus interface* to engine management • Various enhancement options: Modem, printer actuation, Profibus coupling etc.

Hardware • • • •

• • • • •

Input for alternator D+ with pre-excitation for AC alternators 14 terminals for alarm contacts on the RZ 071-D 14 general control inputs on the RZ 071-D 12 relays on the RZ 071-D, 8 of which can be parameterised contact load: • 2 relays max. 35 V, 20 A DC • 10 relays 250 V AC, 6 A Input for pick-up Battery monitor Four slots for analogue input-card modules Two slots for analogue output-card modules Two CAN bus interfaces

Optional functions The hardware must be upgraded accordingly for the software options listed below: • Integration of the automatic control unit in telephone monitoring by means of an internal modem (analogue, ISDN, GSM) • Connection to other systems via Profibus, for example • Event recorder with protocol and fault printout via an RS 232 interface

Hardware options Free analogue signal inputs and outputs can be used as follows: • Relay extension unit RZ 071-E: 15 relays on the RZ 071-E, 14 of which can be parameterised, contact load 250V AC, 6 A • 2 analogue signal outputs 0 – 20 mA or 0 – 10 V • 4 analogue signal inputs, can be equipped for: • Temp. Sensors PT 100 / PT1000, 0-10 V DC, 0-20 mA, NiCr-Ni • Temperature and pressure sensor from MotoMeter, VDO, Noris • PTC thermistor for generator protection* • Measurement of battery charging current* • Modem* (analogue, ISDN, GSM) • Bus coupling units*, e.g. Profibus • Hardware clock with battery back-up*

Technical Data

• Device for panel mounting, Dimensions (WxHxD): 260x170x100 mm • Weight: approx. 2.2 kg, any installation position • Protection type (built-in): IP 44 • Ambient temperature: Storage -20°C ... +70°C Operation 0°C ... +55°C • Standards/regulations: VDE 100/710 • Switchable power supply: 9..12..15 V DC or 14..24..35 V DC * on request

Alfred Kuhse GmbH An der Kleinbahn 39, 21423 Winsen

Tel.: +49 (0)4171 / 798-0 Fax: +49 (0)4171 / 798-117

E-Mail: [email protected] http://www.kuhse.de

Subject to modification Datenblatt_KEA102INSL_de_uk02 Stand: 02/2007

KEA 102 INSL.pdf

Software for sprinkler operation. • For each analogue signal input, actuation of two alarms via. limits. • Two potential-free analogue signal outputs, e.g. for direct.

94KB Sizes 4 Downloads 335 Views

Recommend Documents

KEA 102 INSL.pdf
Alfred Kuhse GmbH, D-21423 Winsen/Luhe, An der Kleinbahn 39. Telefon +49 (0)4171 798-0, Fax +49 (0)4171 798-117, http://www.kuhse.de. Whoops!

KEA 111 ERSY.pdf
Operation mode TEST. − Sprinkler operation. Operation modes 10. Alarm monitoring. − Alarm announcing and acknowledgement. − Description of alarms.

KEA 072 PA.pdf
Probably a protocol converter (available as acces- sory unit) is required for this. TA72PXX.01. September .... KEA 072 PA.pdf. KEA 072 PA.pdf. Open. Extract.

KEA 082 ANL.pdf
2. Page 2 of 12. Page 3 of 12. KEA 082 ANL.pdf. KEA 082 ANL.pdf. Open. Extract. Open with. Sign In. Main menu. Displaying KEA 082 ANL.pdf. Page 1 of 12.

KEA 101 NSTR.pdf
... diodes or other electronic parts of the switchboard may. possibly be damaged. The fuse on the RZ 071-D will be blown, if the control system is connected.

KEA 072 PA.pdf
Technical Data page 23 ... an automation control center), ... made after commissioning, can be taken into ac- count, if they have been previously reported to the.

KEA 083 PST.pdf
Page 1 of 8. Stand 02/ 2000 MULTITESTER I Seite 1. RANGE MAX/MIN VoltSensor HOLD. MM 1-3. V. V. OFF. Hz A. A. °C. °F. Hz. A. MAX. 10A. FUSED.

KEA 101 SPLN.pdf
Replaces: July 2005. Battery Undervoltage. Generator Overload. Failed to Start. Common Alarm. Start Indication. Automatic Mode locked. Alarm Monitoring on.

KEA 111 ERSY.pdf
Parameterisation. − Mains voltage monitor,. − Generator voltage and current monitor,. − Text input (consumer defined) for the first 19. alarms and encoding for all ...

KEA 081 NSTR.pdf
Page 1 of 13. APPLICATION OF AUTOMATIC CONTROL UNIT. The automatic control unit KEA 081-NSTR is ap- plied in emergency power supply installations.

KEA 101 UESY.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. KEA 101 UESY.

KEA 073 PST.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. KEA 073 PST.

KEA 073 PST.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. KEA 073 PST.

102.pdf
Whoops! There was a problem loading this page. Retrying... Whoops! There was a problem loading this page. 102.pdf. 102.pdf. Open. Extract. Open with. Sign In.

102-3a.pdf
Page 1 of 1. 偏遠地區學童衛生常識輔導及測試競賽第 三 期輔導評量試卷. (範圍:登革熱、愛滋病、紅眼症、水痘、H1N1). 1、 (4) 登革熱的傳染一定要有(1)老鼠(2)狗(3) ...

KEA 101 SPL0.pdf
LED TEST button Page 7. − ALARM OFF ... Manual speed control. − Operation mode ... Upgrade options: Modem, printer connection, Profibus coupling etc.

102-Numas.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. 102-Numas.pdf.

102.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. 102.pdf. 102.pdf.

102-2a.pdf
20、 (4) 看書、寫字,光線要充足,而且最好不要(1)從左邊照射(2)從右邊照射(3). 從上面照射(4)從前面直接照射眼睛。 Page 1 of 1. 102-2a.pdf. 102-2a.pdf. Open.

102.PDF
There seems to be little difference regarding small business failure rates between ... agriculture, mining, manufacturing and tourism. Page 3 of 18. 102.PDF. 102.

KEA 111 PANE .pdf
... for the connection of a PC. The following settings (password protected) and analogue readouts are possible. Parameterisation. − Mains voltage monitor,.

KEA 101 & 112 function.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. KEA 101 & 112 ...

KEA 101 SPL0.pdf
... interface (selected by a toggle switch) for the connection of a PC. The following settings (password protected) and analogue readouts are possible. Parameterisation. − Mains voltage monitor,. − Mains failure monitor in parallel mode,. − Gen

CET AD 13-06-11 - KEA
Jun 13, 2011 - M. Arch / MBA (Infrastructure Management) Courses ... The details of academic eligibility for all the above courses are available on the KEA website ... 2.30 pm to 4.30 pm Computer Science, Kuvempu University and.