SA101NX3-E November 2005 Replaces: First edition

Service Manual Start-Stop Control Unit for Emergency Power plants

KEA 101 NSTR

WARNING NOTES − − − − − − − − − − − − − −

Care must be taken when connecting the device, as it may be destroyed if incorrectly connected. All details of the connection specifications must be fulfilled. The PE(N) must be connected for security reasons to terminal 5 on the X403. The leakage current of the noise filters is 22 mA in case of a 2-phase voltage lost. Only adequately qualified personnel should undertake the installation and commissioning. The relevant regulations, especially the VDE regulations, must be observed. The SERVICE MANUAL should be read carefully before commissioning. The device must be parameterised in such a way that any risk to persons or property is prevented. The charging device must be switched off before the battery is disconnected. The negative pole of the battery must be grounded at the input terminal of the switchboard. The minimum conductor cross-section is 10 mm2. The screens of the analogue input wiring must be connected to the earth screws on the KEA cover, and must have no connection to any other metal parts. The supply voltage can be set to 12 or 24 V DC with a switch on the RZ 071-D. When the supply voltage of the control unit has been switched off, you must wait at least 20 seconds before applying it again. All coils must be fitted with reverse diodes to prevent high voltage peaks. All other coils or inductive loads must also be fitted with suppressor elements. The same applies for all relays and inductors that are used in the switchboard or controlled externally. CONTENTS

Design Connection Operation of the display Contrast setting

2 2 3 3

PIN number, IDENT-NUMBER Parameterisation Technical Data Order number codes

3 4 5 6

DOCUMENT HISTORY Revision Date 11/2005 First edition

Modification

Released 05-11-30

Changes without further notice reserved.

Alfred Kuhse GmbH, D-21423 Winsen/Luhe, An der Kleinbahn 39. Phone +49 (0)4171 798-0, Fax +49 (0)4171 798-117, http://www.kuhse.de

SA101NX3-E

-2/6-

11/2005

DESIGN The control unit is incorporate into the front door of the switchboard. The front meets the protection class IP 44 when installed. The two rows of LEDs are marked with interchangeable labels. The relay unit is mounted on the mounting plate and linked to the control unit in the door with the supplied cable. The control unit has an optic fibre or USB interface (selected by a toggle switch) for the connection of a PC. The following settings (password protected) and analogue readouts are possible. Parameterisation Analogue Readouts − Mains voltage monitor, − Actual values: − Generator voltage and current monitor, o Voltages, − Text input (consumer defined) for the first 19 o Currents, alarms and encoding for all alarms, o Active and apparent load, − Battery monitor, o Power factor, − Start-stop parameters, o Speed, − Speed sensing, o Battery voltage, − Mains/generator change-over, o Actual values of the four analogue channels. − Relay and output functions, − Actual status of the digital inputs of the relay unit − Names and limit values for the analogue inputs, RZ 071-D, − Frequency control for isolated operation, − Actual status of the output relays, − Voltage control for isolated operation, − Timers' status. − Internal synchronisation unit, − General parameters. CONNECTION − − − − − − − −

Trained experts may only make the connections of the KEA. The PE(N) must be connected for security reasons to terminal 5 on the X403. The charging device must be switched off before the battery is disconnected. When the supply voltage of the control unit has been switched off, you must wait at least 20 seconds before applying it again. The negative pole of the battery must be grounded at the input terminal of the switchboard. The minimum conductor cross-section is 10 mm2. The supply voltage can be set to 12 or 24 V DC with a switch on the RZ 071-D. The screens of the analogue input wiring must be connected to the earth screws on the KEA cover, and must have no connection to any other metal parts. All coils must be fitted with reverse diodes to prevent high voltage peaks. All other coils or inductive loads must also be fitted with suppressor elements. The same applies for all relays and inductors that are used in the switchboard or controlled externally.

The following signals (if needed) are directly applied to the control unit: − Two analogue output signals, − Voltage of mains and generator, − Optical fibre or USB for parameterisation, − Current of generator, − Two CAN bus systems. − Four analogue sensors, − Pick-up, Although the control system is protected against reverse polarity, the correct polarity when connecting the battery voltage must be strictly observed, as reverse diodes or other electronic parts of the switchboard may possibly be damaged. The fuse on the RZ 071-D will be blown, if the control system is connected with the wrong polarity! Due to the fact that most of the control relays may be configured for various functions, only the status print out of the supplied control unit is to be considered as a binding document. It must be observed, that in case of a possible replacement of a unit, any modifications made after commissioning cannot be taken into account by the manufacturer.

Changes without further notice reserved.

SA101NX3-E

-3/6-

11/2005

OPERATION OF THE DISPLAY Values or parameters are selected, as you would read a book. The further down listed groups are arranged as 'pages'. You can scroll forwards and backwards through these groups by pressing the [→] and [←] keys. The entries of each group can be read from top to bottom like lines of a text. Select a line by pressing the keys [↓] (down) and [↑] (up). The selection starts again with the other end of the 'page', when the top or bottom of the 'page' is reached. Hold down the LED TEST button and press [←] to select directly the ACTUAL VALUES group, hold down LED TEST and press [→] to display the group CURRENT ALARMS. To modify a parameter, first enter the relevant IDENT-NUMBER. However, parameters of group 0, -GENERAL PARAMETERS-, can be modified without entering this number. Parameters are modified as follows: 1. Select the required parameter group with the [←] and [→] buttons. One or two parameters are displayed. 2. Press OFF and LED TEST (function: PARA ON or PARA OFF) together. This opens parameterisation mode as can be seen by the specific cursor [ █ ]. The selection of the group cannot be changed now. 3. Select the required parameter line (if two are displayed) with the [↓] and [↑] buttons. 4. Press OFF and ALARM OFF (ENTER function) together to select the parameter line. The shape of the cursor confirms the selection, as it underscores (e.g. 196) now the part of the parameter that is to be modified. The chosen parameter cannot be deselected now. 5. Select the figure or letter of the parameter that you want to modify with the [←] and [→] cursor keys. Numerical parameters can be increased or decreased by increments of 1 with the [↑] and [↓] buttons. Press the same buttons to negate parameters that are displayed with a letter (+/- signs, alarm coding etc.). 6. Press OFF and ALARM OFF together to store the displayed parameter. Press OFF and LED TEST instead of OFF and ALARM OFF to abort parameterisation. Display contrast setting Hold down LED TEST and press key [↑] to increase the display contrast (makes the display darker) or LED TEST and key [↓] to lower it (makes the display lighter). PIN NUMBER, IDENT-NUMBER To modify a parameter, you first have to enter the relevant IDENT-NUMBER. This number is compared with the PIN NUMBER, and if they are identically, the user is authorised to parameterise the device. The user can chose any PIN NUMBER between 00000 and 50000. The PIN NUMBER and IDENT-NUMBER are factory set to 00000. A special IDENT-NUMBER can be obtained on enquiry from the factory if you forget your PIN NUMBER, so that a new PIN NUMBER can be entered. Modify the PIN NUMBER as follows: − Enter the currently valid IDENT-NUMBER. The pin number is now also shown. − Enter a new PIN NUMBER. − The IDENT-NUMBER previously entered is now no longer valid. The IDENT-NUMBER is deleted 15 minutes after the last input, if the user has not previously set it to an invalid value. The automatic deletion of the IDENT-NUMBER is however not carried out while 00000 is set as the PIN.

Changes without further notice reserved.

SA101NX3-E

-4/6-

11/2005

PARAMETERISATION Menu structure Group 0 KEA 101 NSTR KUHSE GmbH

Group 1 ACTUAL VALUES

Group 2 ENCODING OF ALARMS

Group 3 MAINS VOLTAGE MONITOR

Group 4 GENERATOR VOLTAGE MONITOR GEN.CURRENT MONITOR

Group 5 ANALOGUE INPUTS ANALOGUE

Group 6 SPEED MONITORING SPEED GOVERNOR

Group 7 START-STOP FUNCTIONS

SPEED GOVERNOR

Group 8 ADDITIONAL PARAMETER

Group 9 PARAMETER FOR MAINS <> GEN.

BATTERY VOLTAGE MONOTOR

OUTPUTS

COUNTERS ADDITIONAL TIMERS Group 10

Group 11

RELAY / LED FUNCTIONS

Group 12 FREQUENCY CONTROL VOLTAGE CONTROL

Group 13 THERE ARE NO CURRENT ALARMS

Group 14 THERE ARE NO CURRENT ALARMS

The functions and parameterisation are described in PA100V00-E, FUNCTION BLOCKS AND PARAMETERISATION KEA 101- 112. This document contains all possible functions featured in the KEA Series 101-112. Please note however, that only those functions, listed in the Operation manual, are actually implemented. The PARAWIN parameterisation program also shows only the parameters that are possible for the particular control unit. Group 2 3 4 4 5 5 6 6 7 8 8 8 8 9 10 12 12

Function Encoding of alarms Mains voltage monitor Generator voltage monitor Generator current monitor Analogue inputs Analogue outputs Speed monitoring, speed governor Speed governor Start-stop functions Additional parameters Battery voltage monitor Counters Additional timers Parameters for mains <> generator Relay / LED functions Frequency control Voltage control Connection of KEA and RZ Operation Manual

Section in FUNCTION AND PARAMETERISATION Alarm monitoring Voltage monitor Voltage monitor Current monitor Analogue interface Analogue interface Speed signals and governor Speed signals and governor Parameter for start and stop Additional parameters Additional parameters Additional parameters Additional parameters Transfer mains – generator supply Parameterisation of relays Synchronisation Synchronisation Connection See TA101NX3-D

Changes without further notice reserved.

SA101NX3-E

-5/6-

11/2005

TECHNICAL DATA KEA Controller − Device for frontal installation, dimensions: (⇒,⇑, depth) 260 x 170 x 100 mm, − Weight approx. 2.2 kg, can be installed wherever required, − Protection class (installed) IP 44, − Ambient temperature: Storage -20°C ... +70°C, Operation 0°C … +55°C − Supply voltage convertible 9-12-15V or 14-24-35V DC, − 3 customer defined relays, 35 V DC, 1 A. (e.g. for acoustic signallers), − Standards/regulations VDE 100, Part 710. Analogue Inputs and Outputs − 3-phase mains and generator voltage monitor. They can be set in increments of 1 Volt. If the rotary field is incorrect, the display shows
Changes without further notice reserved.

SA101NX3-E

-6/6-

11/2005

ORDER NUMBER CODES Order number

2A101

Mains Generator 3 x 100 Volt 3 x 100 Volt 3 x 100 Volt 230/400 Volt 3 x 100 Volt 3 x 400 Volt 230/400 Volt 3 x 100 Volt 230/400 Volt 230/400 Volt 230/400 Volt 3 x 400 Volt 3 x 400 Volt 3 x 100 Volt 3 x 400 Volt 230/400 Volt 3 x 400 Volt 3 x 400 Volt Special voltage or frequency CT ../1 A CT ../5 A Special voltage or current measurement

F

U I

N N N N N N N N N N N N N

1 2 3 4 5 6 7 8 9 0

Example: Control unit for emergency power plants, mains and generator voltage 230/400 V, current transformer of generator ../5 A: The order number is 2A101N53

2 3 0

Changes without further notice reserved.

KEA 101 NSTR.pdf

... diodes or other electronic parts of the switchboard may. possibly be damaged. The fuse on the RZ 071-D will be blown, if the control system is connected.

368KB Sizes 5 Downloads 479 Views

Recommend Documents

KEA 101 SPLN.pdf
Replaces: July 2005. Battery Undervoltage. Generator Overload. Failed to Start. Common Alarm. Start Indication. Automatic Mode locked. Alarm Monitoring on.

KEA 101 UESY.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. KEA 101 UESY.

KEA 101 SPL0.pdf
LED TEST button Page 7. − ALARM OFF ... Manual speed control. − Operation mode ... Upgrade options: Modem, printer connection, Profibus coupling etc.

KEA 101 & 112 function.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. KEA 101 & 112 ...

KEA 101 SPL0.pdf
... interface (selected by a toggle switch) for the connection of a PC. The following settings (password protected) and analogue readouts are possible. Parameterisation. − Mains voltage monitor,. − Mains failure monitor in parallel mode,. − Gen

KEA 101 - 112 Function.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. KEA 101 - 112 ...

KEA 111 ERSY.pdf
Operation mode TEST. − Sprinkler operation. Operation modes 10. Alarm monitoring. − Alarm announcing and acknowledgement. − Description of alarms.

KEA 102 INSL.pdf
Software for sprinkler operation. • For each analogue signal input, actuation of two alarms via. limits. • Two potential-free analogue signal outputs, e.g. for direct.

KEA 072 PA.pdf
Probably a protocol converter (available as acces- sory unit) is required for this. TA72PXX.01. September .... KEA 072 PA.pdf. KEA 072 PA.pdf. Open. Extract.

KEA 082 ANL.pdf
2. Page 2 of 12. Page 3 of 12. KEA 082 ANL.pdf. KEA 082 ANL.pdf. Open. Extract. Open with. Sign In. Main menu. Displaying KEA 082 ANL.pdf. Page 1 of 12.

KEA 102 INSL.pdf
Alfred Kuhse GmbH, D-21423 Winsen/Luhe, An der Kleinbahn 39. Telefon +49 (0)4171 798-0, Fax +49 (0)4171 798-117, http://www.kuhse.de. Whoops!

KEA 072 PA.pdf
Technical Data page 23 ... an automation control center), ... made after commissioning, can be taken into ac- count, if they have been previously reported to the.

KEA 083 PST.pdf
Page 1 of 8. Stand 02/ 2000 MULTITESTER I Seite 1. RANGE MAX/MIN VoltSensor HOLD. MM 1-3. V. V. OFF. Hz A. A. °C. °F. Hz. A. MAX. 10A. FUSED.

KEA 111 ERSY.pdf
Parameterisation. − Mains voltage monitor,. − Generator voltage and current monitor,. − Text input (consumer defined) for the first 19. alarms and encoding for all ...

KEA 081 NSTR.pdf
Page 1 of 13. APPLICATION OF AUTOMATIC CONTROL UNIT. The automatic control unit KEA 081-NSTR is ap- plied in emergency power supply installations.

KEA 073 PST.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. KEA 073 PST.

KEA 073 PST.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. KEA 073 PST.

KEA 111 PANE .pdf
... for the connection of a PC. The following settings (password protected) and analogue readouts are possible. Parameterisation. − Mains voltage monitor,.

CET AD 13-06-11 - KEA
Jun 13, 2011 - M. Arch / MBA (Infrastructure Management) Courses ... The details of academic eligibility for all the above courses are available on the KEA website ... 2.30 pm to 4.30 pm Computer Science, Kuvempu University and.

CET AD 13-06-11 - KEA
Jun 13, 2011 - M. Arch / MBA (Infrastructure Management) Courses. Government by its ... 2.30 pm to 4.30 pm Computer Science, Kuvempu University and.

KEA 071 UESY (duits)pdf.pdf
mit Synchronisiergerät: Þ Bestellnummer 2A71U50. Page 3 of 4. KEA 071 UESY (duits)pdf.pdf. KEA 071 UESY (duits)pdf.pdf. Open. Extract. Open with. Sign In.

Kea Every Kiwi Counts 2015 Report.pdf
in Auckland, and the global event series Kea Inspire. • It is free to join Kea - you just have to be passionate about. New Zealand, want to stay connected via our ...

KEA 091 NSTR tech (duits).pdf
Page 1 of 2. Stand 02/ 2000 MULTITESTER I Seite 1. RANGE MAX/MIN VoltSensor HOLD. MM 1-3. V. V. OFF. Hz A. A. °C. °F. Hz. A. MAX. 10A. FUSED.