CAPACITANCE LEVEL SWITCH

http: //www.fine-tek.com e-mail: [email protected] Tel: 886-2-22696789 Fax: 886-2-22686682

4 PRINCIPLE

4 FEATURES AND APPLICATIONS

The capacitance level switch measuring principle is based on the "capacitance effects". When this level switch is set on a silo, it will form a condenser between the detector electrode and the silo wall. The capacitance of this condenser varies proportional to the change of material specific inductivity (DK value) of the material stored in the silo. When the material substances increased in the silo, the capacitance value added simultaneously, then it will let his interior circuit's resonant signal to create a bigger amplitude, and such a signal amplitude become more or less than factory default threshold value, the relay device will be energized. The capacitance value increases as the dielectric increases. Therefore capacitance is proportional to dielectric. When tank is empty, the dielectric of air is 1. As a tank is filled with medium, the amount of capacitance being generated will be increased. This capacitance increase will be detected by the circuit and relay will be activated.

As Capacitance Level Switch has no moving parts inside the device, it will not be affected by friction. It is suitable for powder or liquid application easy to install. The customer can choose the types for his requirements. 1. Standard Type (SA110 & SA111 A/B/C) Suitable for general use. 2. Hi-Temp Type (SA120 & SA128 A/B/C) Suitable for high temperature environment. 3. Anti-Corrosion Type (SA130 & SA132 A/B/C) Suitable for corrosive environment. 4. Remote Probe Type (SA140 A/B/C) For use with vibrator equipped with tank. 5. Wire-Probe Type (SA150 A/B/C) Suitable for silo or deeper tank. 6. Plate-Probe Type (SA160 A/B/C) Suitable for granules and at lower position of tank side. 7. Explosion-Proof Type (SA270 ~ SA279) Ex dia II C T4~T6, DIP A21 TA,T3~T6 8. Explosion-Proof Type (SA370 ~ SA378) Ex ia IIC T3~T6 Equipped with SA-75U signal conditioner can be used in hazardous areas. 9. Anti-Static Type (SA180 & SA181 A/B/C) Suitable for electrostatic environment (It won't be damaged by the electrostatic discharge)

C e

l

2r 2R C= e l /log(R/r)

4 CONSTRUCTION

5. Housing : ADC-12 Aluminum IP65 6. Conduit opening : 1/2"PF or 3/4"PF 7. O-RING : NBR 8. PC board : A, B, C, D Type 9. Sensitivity adjustment : 10pf (std.), 20pf, 40pf 10.Cover ADC-12 Aluminum

1. Probe : SUS304 or SUS316 2. Insulation : UPE or PTFE 3. Grounding Sleeve : SUS304 or SUS316 4. Connection : SUS304 or SUS316 1"PT (default) or 3/4"PT(option)

1

STANDARD TYPE

f118

f118 f118

1/2"PF 1/2"PF

f88

60

1/2"PF 25 1"PT

Dimension

1"PT

25

25

302

1"PT

80

462

402

f21

50

80 f21

50 150(L...)

material

UPE

50

material

UPE

250(L...)

50

Material

250(L...)

PTFE

50

120

f27

120

f12.7 f12.7

Order No.

[ STANDARD TYPE ] SA110 A/B/C

[ STANDARD TYPE ] SA111A/B/C

[ HI-TEMP. TYPE ] SA120 A/B/C

Ambient Temp.

-20LC~60LC

-20LC~60LC

-20LC~60LC

Operating Temp.

-20LC~80LC

-20LC~80LC

-20LC~200LC

Operation Pressure

20kg/cm2

20kg/cm2

20kg/cm2

Probe Material

SUS 304/316

SUS 304/316

SUS 304/316

Insulated Material

UPE

UPE

PTFE

Connection

1"PT Screw (SUS)

1"PT Screw (SUS)

1"PT Screw (SUS)

Sensitivity Range

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

Weight

Approx. 1.9kg

Approx. 1.9kg

Approx. 2.4kg

Housing Spec.

Aluminum IP65

Supply Voltage

110/220VacK10% or 16~24Vdc

Delay Time

0~6 sec

Power Consumption

2W

Output Rating

Relay: 5A/250Vac or 5A/30Vdc,NPN 100mA

If length of sensing probes is longer than 3 meters, please choose 20pf or 40pf sensitivity type.

2

STANDARD TYPE

f118

f118

f118

1/2"PF

1/2"PF 1/2"PF

f140

f140

145

Dimension

14

f155

25 105

620

413

4- f19

4- f19

130

4- f15

PVDF

255

250

250(L...)

material

UPE

330(L...)

f55

105

Material

Material

PP

40

Material

CERAMIC

40 f40

f28

f25

Order No.

[SUPER HI-TEMP. TYPE ] SA128 A/B/C

Ambient Temp.

-20LC~60LC

-20LC~60LC

-20LC~60LC

Operating Temp.

-20LC~800LC

-20LC~80LC

-20LC~120LC

Operation Pressure

ATM

20kg/cm2

20kg/cm2

Probe Material

SUS 304/316

SUS 304 Coating PP

SUS304 Coating PVDF

Insulated Material

CERAMIC

UPE

UPE

Connection

2-1/ 2"x5kg/cm2 Flange(SUS)

1-1/2"x10kg/cm2 Flange(PP)

1-1/2"x10kg/cm2 Flange(SUS) (5mm PVDF)

Sensitivity Range

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

Weight

Approx. 6.5kg

Housing Spec.

[ CORROSION-PROOF TYPE ] [ CORROSION-PROOF TYPE ] SA130 A/B/C SA132 A/B/C

Approx. 2kg Aluminum IP65

Supply Voltage

110/220VacK10% or 16~24Vdc

Delay Time

0~6 sec

Power Consumption

2W

Output Rating

Relay: 5A/250Vac or 5A/30Vdc,NPN 100mA

If length of sensing probes is longer than 3 meters, please choose 20pf or 40pf sensitivity type.

3

STANDARD TYPE

f118

d. = 77

112

Std.:1.8m Max.:5m f65

1/2"PF Material

195

25 1"PT

1"PT

1/2"PF 2- f7.5

80

356 f21

UPE

80

f155

f21

25

Dimension

290

50 Material

250(L...)

4-f15 f130

f9

Material

UPE

f118

f 96

70

UPE 5m(L...)

50

f75

1/2"PF 150

120

186 M8

150

f12.7

Order No.

[ REMOTE PROBE TYPE ] SA140 A/B/C

[ WIRE-PROBE TYPE ] SA150 A/B/C

[ PLATE TYPE ] SA160 A/B/C

Ambient Temp.

-20LC~60LC

-20LC~60LC

-20LC~60LC

Operating Temp.

-20LC~80LC

-20LC~80LC

-20LC~80LC

Operation Pressure

20kg/cm2

20kg/cm2

20kg/cm2

Probe Material

SUS 304/316

Insulated Material

UPE

UPE

UPE

Connection

1"PT Screw (SUS)

1"PT Screw (SUS)

2-1/2"x 5kg/cm2 Flange (SUS)

Sensitivity Range

10pf (std.)

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

Weight

Approx. 3kg

Approx. 4.1kg

Approx. 3.2kg

SUS 304/316 cable

SUS 304/316

Housing Spec.

Aluminum IP65

Supply Voltage

110/220VacK10% or 16~24Vdc

Delay Time

0~6 sec

Power Consumption

2W

Output Rating

Relay: 5A/250Vac or 5A/30Vdc,NPN 100mA

If length of sensing probes is longer than 3 meters, please choose 20pf or 40pf sensitivity type.

4

STANDARD TYPE

f118

f118

1/2"PF 1/2"PF

f88

60 25 1"PT

25

Dimension

1"PT

412

472

260~1500(Max.) Material UPE

260~1500(Max.)

Material

PTFE f21

f21

Order No.

[ ANTI-STATIC TYPE ] SA180 A/B/C

[ HI-TEMP ANTI-STATIC TYPE ] SA181 A/B/C

Ambient Temp.

-20LC~60LC

-20LC~60LC

Operating Temp.

-20LC~80LC

-20LC~200LC

Operation Pressure

20kg/cm2

20kg/cm2

Probe Material

UPE Coating

PTFE Coating

Insulated Material

UPE

PTFE

Connection

1"PT Screw (SUS)

1"PT Screw (SUS)

Sensitivity Range

10pf (std.) 20pf (option)

10pf (std.) 20pf (option)

Weight

Approx. 2kg

Approx. 2.5kg

Housing Spec.

Aluminum IP65

Supply Voltage

110/220VacK10% or 16~24Vdc

Delay Time

0~6 sec

Power Consumption

2W

Output Rating

Relay: 5A/250Vac or 5A/30Vdc,NPN 100mA

If length of sensing probes is longer than 3 meters, please choose 20pf or 40pf sensitivity type.

5

EXPLOSION PROOF TYPE

f113 f113 1/2"NPT

f113

108

1/2"NPT

108

1/2"NPT

f88

108

60 25

Dimension

1"PT

25

1"PT

50 Material

25

302

1"PT

80

50 150(L...)

Material

UPE

462

402

f21

80 f21

50 250(L...)

PTFE

Material

50 250(L...)

PTFE

50 f27

f12.7

120

120 f12.7

Order No.

[ STANDARD TYPE ] SA270

[ STANDARD TYPE ] SA271

[ HI-TEMP. TYPE ] SA272

Ambient Temp.

-20LC~60LC

-20LC~60LC

-20LC~60LC

Operating Temp.

-20LC~80LC

-20LC~80LC

-20LC~200LC

Operation Pressure

20kg/cm2

20kg/cm2

20kg/cm2

Probe Material

SUS 304/316

SUS 304/316

SUS 304/316

Insulated Material

UPE

UPE

PTFE

Connection

1"PT Screw (SUS)

1"PT Screw (SUS)

1"PT Screw (SUS)

Sensitivity Range

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

Weight

Approx. 1.9kg

Approx. 2.4kg

Approx. 4.1kg

Housing Spec.

Aluminum IP65

Supply Voltage

110/220VacK10% or 16~24Vdc

Enclosure Protection

Ex dia II C T4~T6, DIP A21 TA, T3~T6

Power Consumption

2W

Output Rating

Relay: 5A/250Vac or 5A/30Vdc,NPN 100mA

If length of sensing probes is longer than 3 meters, please choose 20pf or 40pf sensitivity type.

6

EXPLOSION PROOF TYPE

f113

f113 1/2"NPT

f113 1/2"NPT

1/2"NPT

108 108

108

f140

25

f140

1"PT

290

80

f21

Dimension

25 105

413

50

4- f19

105

Material

4- f19

PVDF

255

Material PTFE

L

70

3m(L...)

Material

UPE

f9

Material

PP

f40

Order No.

M8

f25

[ CORROSION-PROOF TYPE ] [ CORROSION-PROOF TYPE ] SA273 SA274

150

[ WIRE-PROBE TYPE ] SA275

Ambient Temp.

-20LC~60LC

-20LC~60LC

-20LC~60LC

Operating Temp.

-20LC~80LC

-20LC~120LC

-20LC~80LC

Operation Pressure

ATM

20kg/cm2

20kg/cm2

Probe Material

SUS 304/316(PP Coating)

SUS 304/316(PVDF Coating)

SUS 304/316 Cable

Insulated Material

UPE

PTFE

PTFE

Connection

1-1/2"x10kg/cm2 (PP)

1-1/2"x10kg/cm (SUS) W / PVDF Coating

1"PT Screw (SUS)

Sensitivity Range

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

Weight

Approx. 1.9kg

2

Approx. 4.1kg

Housing Spec.

Aluminum IP65

Supply Voltage

110/220VacK10% or 16~24Vdc

Enclosure Protection

Ex dia II C T4~T6, DIP A21 TA, T3~T6

Power Consumption

2W

Output Rating

Relay: 5A/250Vac or 5A/30Vdc,NPN 100mA

If length of sensing probes is longer than 3 meters, please choose 20pf or 40pf sensitivity type.

7

EXPLOSION PROOF TYPE

f113

f113

1/2"NPT

1/2"NPT

108

108

Material

1/2"NPT

UPE

f88

60 25

f155

1"PT

Dimension

f 96

f75

f113

25

412

1"PT 472 4-f15 f130

260~1500(Max.)

108

150

260~1500(Max.)

Material

PTFE f21

186

Material

PTFE f21

Max.180

Max.180

Order No.

[ PLATE TYPE ] SA276

[ HI-TEMP ANTI-STATIC TYPE ] SA277

[ ANTI-STATIC TYPE ] SA278

Ambient Temp.

-20LC~60LC

-20LC~60LC

-20LC~60LC

Operating Temp.

-20LC~80LC

-20LC~200LC

-20LC~80LC

Operation Pressure

20kg/cm2

20kg/cm2

20kg/cm2

Probe Material

SUS 304/316

PTFE or UPE Coating

PTFE or UPE Coating

Insulated Material

PTFE or UPE

PTFE or UPE

PTFE or UPE

1"PT Screw (SUS)

1"PT Screw (SUS)

2 Connection 2-1/2"x 5kg/cm Flange (SUS)

Sensitivity Range

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf (option)

Weight

Approx. 3.2kg

Approx. 3.1kg

Approx. 2kg

Housing Spec.

Aluminum IP65

Supply Voltage

110/220VacK10% or 16~24Vdc

Enclosure Protection

Ex dia II C T4~T6, DIP A21 TA, T3~T6

Power Consumption

2W

Output Rating

Relay: 5A/250Vac or 5A/30Vdc,NPN 100mA

If length of sensing probes is longer than 3 meters, please choose 20pf or 40pf sensitivity type.

8

INTRINSICALLY SAFE EXPLOSION PROOF TYPE

f113 f113 1/2"NPT

f113

108

1/2"NPT

108

1/2"NPT

f88

108

60 25

Dimension

1"PT

25

1"PT

50 Material

25

302

50 150(L...)

UPE

1"PT

80

80 f21

50

Material UPE

250(L...)

50

Material

250(L...)

PTFE

50 f27

462

402

f21

f12.7

120

120 f12.7

Order No.

[ STANDARD TYPE ] SA370 (WITH SA-75U)

[ STANDARD TYPE ] SA371 (WITH SA-75U)

[ HI-TEMP. TYPE ] SA372 (WITH SA-75U)

Ambient Temp.

-20LC~60LC

-20LC~60LC

-20LC~60LC

Operating Temp.

-20LC~80LC

-20LC~80LC

-20LC~200LC

Operation Pressure

20kg/cm2

20kg/cm2

20kg/cm2

Probe Material

SUS 304/316

SUS 304/316

SUS 304/316

Insulated Material

UPE

UPE

PTFE

Connection

1"PT Screw (SUS)

1"PT Screw (SUS)

1"PT Screw (SUS)

Sensitivity Range

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

Weight

Approx. 1.9kg

Approx. 2.4kg

Approx. 2.4kg

Housing Spec.

Aluminum IP65

Supply Voltage

16~24Vdc

Enclosure Protection

Ex ia IIC T3~T6

Power Consumption

2W

Output Rating

NPN 100mA

If length of sensing probes is longer than 3 meters, please choose 20pf or 40pf sensitivity type.

9

INTRINSICALLY SAFE EXPLOSION PROOF TYPE

f113

f113 1/2"NPT

f113 1/2"NPT

1/2"NPT

108 108

108

f140

25

f140

1"PT

290

80

f21

Dimension

25 105

413

50

4- f19

105

Material

4- f19

PVDF

255(L...)

Material PTFE

L

70

3m(L...)

Material

UPE

f9

Material

PP

f40

Order No.

M8

f25

[ CORROSION-PROOF TYPE ] [ CORROSION-PROOF TYPE ] SA373 (WITH SA-75U) SA374 (WITH SA-75U)

150

[ WIRE-PROBE TYPE ] SA375 (WITH SA-75U)

Ambient Temp.

-20LC~60LC

-20LC~60LC

-20LC~60LC

Operating Temp.

-20LC~80LC

-20LC~120LC

-20LC~80LC

Operation Pressure

ATM

20kg/cm2

20kg/cm2

Probe Material

SUS 304/316(PP Coating)

SUS 304/316 W / PVDF Coating

SUS 304/316 Cable

Insulated Material

UPE

PTFE

PTFE

Connection

1-1/2"x10kg/cm2 (PP)

1-1/2"x10kg/cm2 (SUS) W / PVDF Coating

1"PT Screw (SUS)

Sensitivity Range

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

Weight

Approx. 1.9kg

Approx. 4.1kg

Housing Spec.

Aluminum IP65

Supply Voltage

16~24Vdc

Delay Time

Ex ia IIC T3~T6

Power Consumption

2W

Output Rating

NPN 100mA

If length of sensing probes is longer than 3 meters, please choose 20pf or 40pf sensitivity type.

10

INTRINSICALLY SAFE EXPLOSION PROOF TYPE

f113

f113 1/2"NPT

1/2"NPT

108 Material

108

1/2"NPT

UPE

f88

60

25

f155

Dimension

1"PT

f 96

f75

f113

25

412

1"PT 472 4-f15 f130

260~1500(Max.)

108

150 186

260~1500(Max.)

Material

PTFE f21

Material UPE

Max.180

f21

Max.180

Order No.

[ PLATE TYPE ] SA376 (WITH SA-75U)

[ HI-TEMP ANTI-STATIC TYPE ] SA377 (WITH SA-75U)

[ ANTI-STATIC TYPE ] SA378 (WITH SA-75U)

Ambient Temp.

-20LC~60LC

-20LC~60LC

-20LC~60LC

Operating Temp.

-20LC~80LC

-20LC~200LC

-20LC~80LC

Operation Pressure

20kg/cm2

20kg/cm2

20kg/cm2

Probe Material

SUS 304/316

PTFE Coating

UPE Coating

Insulated Material

UPE

PTFE

UPE

1"PT Screw (SUS)

1"PT Screw (SUS)

2 Connection 2-1/2"x 5kg/cm Flange (SUS)

Sensitivity Range

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf, 40pf (option)

10pf (std.) 20pf (option)

Weight

Approx. 3.2kg

Approx. 3.1kg

Approx. 2kg

Housing Spec.

Aluminum IP65

Supply Voltage

16~24Vdc

Delay Time

Ex ia IIC T3~T6

Power Consumption

2W

Output Rating

NPN 100mA

If length of sensing probes is longer than 3 meters, please choose 20pf or 40pf sensitivity type.

11

SA-75U INTRINSIC SAFE SIGNAL CONDITIONER

16Vdc SIGNAL INPUT

0V

SA-75U Zener barriers inside provide intrinsic safety to SA179D type level switch. The unit works via a current-limiting feature which protects the device from damage by emission of sparks.

PWR ON

75

SA-75U

1. Supply voltage :

110 / 220Vac

2. Power consumption : 2W 3. Input signal :

NPN transistor resistance Ri= 500W

4. Output voltage :

16~24 Vdc

0V 220V COM 110V NC NO

5. Short circuit current : 25mA max. 6. Relay output :

SPDT 10A /30Vdc 10A /220Vac

7. Operating temp. :

-20BC ~ 60BC

8. Weight :

0.3 kg

9. Enclosure rating :

Ex (ia) IIC T6

45

110

4 WIRING CONFIGURATION Wall

(Hazardous area) SA179D

(Non-hazardous area)

SA-75U

16Vdc

AWG 18H3C electric cable

IN

SA-75U

Remote Control Room

12

ADJUSTMENT

4 COARSE CALIBRATION

4 DELAY FUNCTION CALIBRATION

Set the "Sensitive ADJ. " to the "H" position. Then use a screw driver to adjust the "Coarse" until indicator is lighted. At last check "Indicator" is light or not by adjust the "Sensitivity Adj" knob, if not, repeat procedure.

The default setting is 0 second, here at the material is in contact with probe will illuminate "Indicator" lamp and energize relay. When the user need to use this delay function, please set timer in clockwise. The relay will energized after "Indicator" illuminate for several seconds if set timer more than 0 second. The delay function is suitable for variable material level. e.g. liquid tank equip with agitator.

4 SENSITIVITY ADJUSTMENT When the material is out of contact with probe will extinguish the "Indicator". When the material is in contact with probe will illuminated the "Indicator " lamp, at this time please adjust "Sensitivity ADJ." until lamp is in extinction. And then set "Sensitivity ADJ." in the middle between "H" and extinction position. e.g. If extinction position is 10p, you should set "Sensitivity ADJ." in "75" position.

SENSITIVITY ADJ. 60

50

40

70

30

80

20

90

10 L

H

SA140 LEVLE SENSOR

INDICATOR

SERIES No.

DELAY

SENSITIVITY-No.

COARSE

E

S

C

A

B

0V

110V 220V

SA-TYPE LEVEL SENSOR SERIES No. SENSITIVITY-No.

10

90

20

80

SENSITIVITY ADJ 60 50 40 3 0 70

H

L

Braided shield

INDICATOR

DELAY

To sensor coaxial cable C=120 ~ 135

COARSE NC

NO COM

AC0V 110V 220V

Remote Probe Type (SA140 A/B/C) Normal close Normal open Common

Power Source

SA110, 120, 130, 150, 160, 179, 180 A/B/C/D

13

Power Source Normal close Normal open Common

INSTALLATION NOTICE

A

A Connecting pipe

25mm max.

B

B

a B

f100 L L>30mm

A

SA110

The insensible portion should be mounted to protrude 30mm from the vessel wall. That's to prevent malfunction from a fill material or an insufficient clearance between probe and connection pipe.

SA160

SA160 to be mounted properly, the vessel walls should not exceed 25mm.

To prevent false readings, users have to make sure the material flows symmetrically. If the inlet is not located in the center portion of the tank roof, check the flow pattern (a angle) of your material and place the probe in the appropriate location.

SA150

300mm

SA140

SA160

If the probe is mounted on the top, make sure the length of probe long enough to touch the highest level of raw material. SA150 type must have at least 300mm from the electrode probe to the silo wall. SA160 type is usually installed at the lower of tank side.

For Non-Stationary or vibrating environment, a separate control unit such as the SA140 is suggested.

14

It is suggested to install the probe away from the inlet to reduce the risk of inflowing material damaging the probe. If the probe is near an inlet, it is recommended to place a protective cover 200mm above the probe. The cover should be parallel to the probe and the same length.

INSTALLATION NOTICE

300mm

300mm

If two parallel probes are mounted, they must be installed separately at least 300 mm to minimize interference .

The probe should not be mounted underneath a liquid inlet, otherwise it will switch on erroneously.

If the tank equips with agitator, please use the time-delay type (SA999 -A~D) to prevent fault level detection.

Mounting the probe at a 20B incline will optimize the results and increase sensitivity. It also won't be damaged by the inflowing material.

Mounting the probe at top of tank can avoid material bridges from forming. It's helpful to record accurate measurements.

20L

The cable inlet should face downward to avoid rain damage. Tighten the cable with the connecting part.

15

ORDER INFORMATION

SA 1 1 0 A D Q ( 1 0 0 0 ) Model 110 --- Standard Type 120 --- Hi-temp. Type 130 --- Corrosion Proof Type 140 --- Remote Probe Type 150 --- Wire Probe Type 160 --- Plate Type 180 --- Anti-Static Type 279 --- Explosion Proof Type 379 --- Explosion Proof Type

Terminal Arrangement A---110/220Vac, Relay output B---24Vdc, Relay output C---24Vdc, NPN transistor output D---Designed for use with SA-75U 0 110 220

SA999 A

SA999 B

0 24

110V/220VAC

DC24V

Relay output

Relay output

SA999 C

SA379 D

16~

DC24V Transistor npn output

0V 24V OUT

Ex (ia) IIC Control unit output

0V 24V OUT

R

0V

NO COM NC 220V 110V 0V

INPUT 16VDC 0V

+24Vdc

RELAY OUTPUT

AC SUPPLY

SA-75U

External power supply

Connection C---3/4"(20A) D---1"(25A) E---1-1/2"(40A) F---2"(50A) G---2-1/2"(65A) H---3"(80A) I ---4"(100A) J---5"(125A) K---6"(150A) S---Others

M---5kg/cm 2 N---10kg/cm 2 O---150 Lbs P---300 Lbs Q---PT R---PF(G) T---BSP U---NPT S---Others

W---PN 10 X---PN 16 Y---PN 25 Z---PN 40

Probe Length (mm) 0500: 50cm (01~50) 1000: 100cm (51~100) 1500: 150cm (101~150)

50cm per Unit

Q Tolerance of the total product length is K5mm. Q Characteristics, specifications and dimensions are subject to change without notice. Q Please contact your nearest distributor office for further informations.

16

CAPACITANCE LEVEL SWITCH

timer in clockwise. The relay will energized after. "Indicator" illuminate for several seconds if set timer more than 0 second. The delay function is suitable for ...

2MB Sizes 2 Downloads 293 Views

Recommend Documents

CAPACITANCE LEVEL SWITCH
circuit and relay will be activated. As Capacitance Level Switch has no moving parts inside the device, it will not be affected by friction. It is suitable for powder or liquid application easy to install. The customer can choose the types for his re

Capacitors - Capacitance, Charge and Potential Difference
In each case, calculate the capacitance of the capacitor: In each case, calculate the charge stored on the plates of the capacitor: In each case, calculate the potential difference between the plates of the capacitor: ○ charge stored on capacitor p

Gate capacitance in electrochemical transistor of single ...
and Fermi–Dirac distribution at T=290 K as follows: Q(Vchem) = 0. D(E) exp[(E − eVchem)/kBT] + 1. dE, where kB is Boltzmann constant. Using the equation, the.

Cheap Newest 1Pcs Free Tv Diseqc Switch 4X1 Diseqc Switch ...
Cheap Newest 1Pcs Free Tv Diseqc Switch 4X1 Diseqc ... For Tv Receiver Free Shipping & Wholesale Price.pdf. Cheap Newest 1Pcs Free Tv Diseqc Switch ...

Cheap Diseqc Switch 4X1 Diseqc Switch Satellite Antenna Flat Lnb ...
Cheap Diseqc Switch 4X1 Diseqc Switch Satellite Ante ... For Tv Receiver Free Shipping & Wholesale Price.pdf. Cheap Diseqc Switch 4X1 Diseqc Switch ...

SWITCH eng.pdf
These are mostly SMD components. The processor is in the THT, which will. facilitate the exchange of. Page 3 of 10. SWITCH eng.pdf. SWITCH eng.pdf. Open.

Slide switch plug
#define second_led 13 ​//second LED is connected to 13th pin. #define first_datapin 10 ​//D1 of slide switch is connected to. 10th pin. #define second_datapin ...

Light triggered light switch
Dec 25, 2012 - ee app lcanon e or Comp ete Seam lstory' is actuated by light of su?icient .... Will be used to make this calculation. Where no is 4 pi>

Characteristic trapping lifetime and capacitance-voltage ...
are necessary to complement the room temperature data in order to gather ... measurements and secure conclusions on the density of interface states can only ...

Capacitance-Voltage (CV) Characterization of GaAs ...
energies, an electron trap peak close to mid-gap energies and an electron trap ..... The authors acknowledge support by the European Commission's project ...

Gate capacitance in electrochemical transistor of single ...
electrodes (Pt–Au) were formed on a SWNT with electron- beam lithography.8 ... devices measured by an atomic force microscope were. 1.3–1.7 nm and ...

Hero Build Level 1 Level 4 Level 7 Level 10 Level 13 Level ... - GitHub
Metamorphosis. 2. 2. 2. 1. 3. 1. 1. Illidan. Standard Split. 1. 2. 2. 2. 3. 1. 4. Jaina. Frostbolt. 3. 1. 2. 2. 3. 3. 2. Johanna. Defensive. 3. 2. 3. 2. 2. 1. 3. Johanna ... Balanced. 3. 3. 1. 2. 1. 2. 3. Nazeebo. Spider 2.0. 1. 1. 1. 2. 3. 3. 4. Naz

A Capacitance-Compensation Technique for Improved ...
These simplifications are justified, since the purpose of the model is merely to illustrate the main sources of nonlinearity under class-AB operation. For accurate simulation re- sults needed in final designs, however, it should be noted that radio-f

Investigation of the capacitance deviation due to metal ...
In this paper, the influence of floating dummy metal- fills on interconnect parasitic is analyzed with the varia- tions of possible factors which can affect the capacitance. Recently proposed chip-level metal-fill modeling, replac- ing metal-fill lay

Formula-Based Method for Capacitance Extraction of ...
[12] Y. Chen, P. Gupta, and A.B. Kahng, “Performance-impact limited area fill ..... From 1991 to 2000, he is with Device Development Center, Hitachi Ltd.,.

SlidE switch plug
27 Nov 2017 - Product Manual: Slide Switch Plug. Index. Introduction. 2. Specification. 2. Variants. 2. Supported cables: 3. Details. 3. How to interface? 4. Example Codes. 6. Code 1: Arduino. Elint Labz (​www.elintlabz.in​). Page 1 of 7 ...

Switch Guiding Statements.pdf
Children will be supported by healthy school and home environments to switch what they Do,. View, and Chew. • Objectives. – Children will: • Switch up to 60 ...

TIMESTAMP LIQUID LEVEL (LTS) LOW LEVEL ALARM HIGH LEVEL ...
TIMESTAMP. LIQUID LEVEL (LTS). LOW LEVEL ALARM. HIGH LEVEL ALARM. 8/10/2017 9:27:11. 115. 0. 0. 8/10/2017 10:10:05. 115. 0. 0. 9/15/2017 13:52:06.

Cheap G-Box 4X1 Diseqc Switch Satellites Fta Tv Lnb Switch For ...
Cheap G-Box 4X1 Diseqc Switch Satellites Fta Tv Lnb S ... atellite Receiver Free Shipping & Wholesale Price.pdf. Cheap G-Box 4X1 Diseqc Switch Satellites Fta ...

Grove - Magnetic Switch v1.3.sch - GitHub
Page 1. 1. 2. 3. 4. 1. 1. 2. 2. A. B. C. D. 1. 2. 3. 4. 5. 6. A. B. C. D. 1. 2. 3. 4. 5. 6.

ZL7432-In-Wall-Switch-Manual.pdf
Thanks for choosing the Vision's In-Wall Switch module of the home automation device. This module is a Z-WaveTM enabled device (interoperable, two-way RF ...