APPLICATION OF ABRUPT CHANGE DETECTION IN RELAY PERFORMANCE MONITORING A. Ukil (1), R. Zivanovic (1) (1) Tshwane University of Technology, Pretoria, South Africa

ABSTRACT This paper describes the application of the abrupt change detection technologies to detect the abrupt changes in the signals recorded during disturbances in the electrical power network of South Africa for monitoring the relay performance. Main focus has been to estimate exactly the time-instants of the changes in the signal model parameters during the pre-fault condition, after initiation of fault, after circuit-breaker opening and auto-reclosure of the circuit-breakers. After segmenting the fault signal precisely into these event-specific sections, synchronization of the different digital fault recorder (DFR) recordings are done based on the fault inception timings. This is essential as the timebases of the DFRs triggering for the same disturbance are not perfectly synchronized. The synchronized signals are segmented again and the synchronized, segmentations are used to analyze the performances of the protective relays during the disturbance. Keywords: Abrupt change detection, Wavelet transform, Synchronization, Relay performance INTRODUCTION Automatic disturbance recognition and analysis from the recordings of the digital fault recorders (DFRs) play a significant role in fast fault-clearance, helping to achieve a secure and reliable electrical power supply. Segmentation of the fault recordings by detecting the abrupt changes in the characteristics of the fault recordings, obtained from the DFRs of the power network in South Africa, is the first step towards automatic disturbance recognition and analysis. Besides facilitating the subsequent automatic disturbance recognition and analysis, abrupt change detection based segmentation also helps in monitoring the performances of the protective relays during the disturbances. To accomplish the abrupt change detection, we propose the use of the wavelet transform to transform the original fault signal into finer wavelet scales, followed by a progressive search for the largest wavelet coefficients on that scale [1]. Large wavelet coefficients that are co-located in time across different scales provide estimates of the changes in the signal parameter. The change time-instants can be estimated by the number of wavelet coefficients that exceed a given threshold (which is equal to the ‘universal threshold’ of Donoho and Johnstone [2] to a first order of approximation). After the segmentation, the segmented fault recordings, from the different DFRs triggering for the same disturbance are synchronized depending on the fault inception timings. This is essential as the timebases of the DFRs triggering for the same disturbance are not perfectly synchronized [3]. The synchronized analog signals are segmented once again using the abrupt change detection

technologies. The synchronized, segmented analog signals are then compared against the recorded binaries, also synchronized following the corresponding analog signals, for monitoring the relay performance during the disturbance. AUTOMATIC FAULT ANALYSIS Automatic fault analysis of the disturbances in the transmission network of South Africa depends on the DFR recordings. Presently, 98% of the transmission lines are equipped with the DFRs on the feeder bays, with an additional few installed on the Static Var Compensators (SVCs) and 95% of these are remotely accessible via a X.25 communication system [4]. The DFRs trigger due to reasons like, power network fault conditions, protection operations, breaker operation and the like. Following IEEE COMTRADE standard [5], the DFR recordings are provided as input to the fault analysis software which uses Discrete Fourier Analysis and Superimposed current quantities [4]. The purpose of this study is to augment the existing semi-automatic fault analysis system with more robust and accurate algorithms and techniques to make it fully automated. So, we would first apply the abrupt change detection algorithms to segment the fault recordings into different segments, viz., pre-fault segment, after initiation of fault, after circuit-breaker opening, after auto-reclosure of the circuit-breakers. Then we would construct the appropriate feature vectors for the different segments; finally the pattern-matching algorithm would be applied using those feature vectors to accomplish the fault recognition and analysis tasks.

The first step towards the proposed automatic fault analysis, viz. the abrupt change detection based segmentation is quite critical for improving the fault recognition rate and automatic analysis quality. It also provides a great scope for monitoring the performances of the protective relays directly from the segmented recordings before conforming to any further significant and complex feature vector analysis. This is focussed in the scope of this paper. ABRUPT CHANGE DETECTION The authors have already discussed different technologies for abrupt change detection in a comparative manner in [6]. The techniques are broadly categorized as Simple methods, Linear model-based approach, Model-free approach and Non-parametric approach [6]. Among these techniques, the Non-parametric approach, viz., the wavelet transform appears to be most suitable for this specific application. Detail description of the abrupt change detection using the wavelet transform and threshold checking can be referred to in [7]. We only provide the summary of the abrupt change detection using the wavelet transform in the following sections.

wavelets are used as the mother wavelets. After transforming the original fault signal using the mother wavelets and DWT, we obtain the smoothed and detailed versions [7]. The detailed version, called the wavelet transform coefficient, is used for threshold checking to estimate the change time-instants [7]. Application of Threshold Method As wavelet coefficients are the changes of the averages, so a coefficient of large magnitude implies a large change in the original signal [7]. The change timeinstants can be estimated by the instants when the wavelet coefficients exceed a given threshold which is equal to the ‘universal threshold’ of Donoho and Johnstone [2] to a first order of approximation. The universal threshold T is given by

T = σ 2 log e n ,

(4)

where σ is the median absolute deviation of the wavelet coefficients, divided by 0.6725 [2] and n is the number of samples of the wavelet coefficients. Example Result Figure 1 shows the abrupt change detection result using the wavelet transform and threshold method.

Wavelet Decomposition The continuous wavelet transform (CWT) is defined as the sum over all time of the signal multiplied by scaled and shifted versions of the wavelet function ψ . The CWT of a signal x(t) is defined as ∞

CWT (a, b) =

∫ x(t )ψ a,b (t )dt , *

(1)

−∞

where,

ψ a ,b (t ) = a

−1 / 2

ψ ((t − b) / a ) .

(2)

ψ (t ) is the mother wavelet, the asterisk in (1) denotes a complex conjugate, and a, b ∈ R, a ≠ 0, (R is the real continuous number system) are the scaling and shifting parameters respectively. The discrete wavelet transform (DWT) is given by choosing a = a 0m , b = na 0m b0 , t = kT in (1) & (2), where T = 1.0 and k, m, n ∈ Z , (Z is the set of positive integers).

DWT (m, n) =

a 0− m / 2

(∑ x[k ]ψ

*

[( k

).

− na 0m b0 ) / a 0m ]

(3) We apply the Multiresolution Signal Decomposition (MSD) [8] technique and Quadrature Mirror Filter (QMF) [8] banks to decompose the fault signals from the DFRs into localized and detailed representation in the form of wavelet coefficients. Daubechies 1 and 4 [9]

Figure 1 Segmentation of BLUE-phase Voltage

In Figure 1, the original DFR recording from the Eskom transmission network for the voltage during the fault in the BLUE-Phase, sampled at a frequency of 2.5 KHz [4], is shown in the top section; wavelet coefficients for this fault signal and the universal threshold (dashed) are shown in the middle section and the change timeinstants as unit impulses computed using the threshold checking (middle section) followed by smoothing

filtering [7] are shown in the bottom section. It is to be noted that only the high-pass filter output of the QMF pair is shown, so the wavelet coefficients in the middle section indicate half of the total samples of the original signal [7]. The time-instants of the changes in the signal characteristics in the lower plot in Figure 1 indicate the different signal segments owing to different events during the fault, e.g., segment A indicates the pre-fault section and the fault inception, segment B indicates the fault, segment C indicates opening of the circuitbreaker, segment D indicates auto-reclosing of the circuit-breaker and system restore. SYNCHRONIZATION

Usually many DFRs, employed for different distance protection zones, trigger for any abnormal condition in the power network. All these simultaneous recordings only differ by some time-delays. First, all these simultaneous recordings are segmented using the abrupt change detection method described above. But before any further global analysis, an important step is required, viz., ‘Synchronization’. This is essential as the timebases of the DFRs triggering for the same disturbance are not perfectly synchronized [3] and that can lead to erroneous conclusions especially when analyzing the performances of the protective relays etc during the disturbance. In Figure 2, we show the voltage recordings of three different DFRs triggering for the same phase-to-ground fault involving the BLUE-phase.

Figure 2 Three DFR recordings for the same event

As described above, first all the recordings are segmented using the abrupt change detection method. And this is reflected in all of the three plots in Figure 2 by the

dashed vertical lines, segmenting the voltage signals into segments like A, B, C, D. For all of them, segment A indicates the pre-fault section and the fault inception, segment B indicates the fault, segment C indicates opening of the circuit-breaker, segment D indicates auto-reclosing of the circuit-breaker and system restore. Clearly from the figure, all these segments are not synchronized for the three recordings although they essentially represent the same event. To synchronize the recordings for further analysis, we will use the fault inception timing, i.e., the borderline between the segment A and B in all of the segmented recordings. It is to be noted that in Figure 2, the X-axis indicates the number of samples, so we have to divide it by the sampling frequency of 2.5 KHz to get the fault inception time in milliseconds. Table-1 lists the fault inception timings of the three DFR recordings shown in Figure 2. Table 1 Fault Inception Time of the DFR recordings Recordings

DFR-1 DFR-2 DFR-3

Fault Inception Time

Fault Inception Time

(Sample No.)

(Milliseconds)

938 2410 770

375.2 964 308

The complete synchronization algorithm is described below. ƒ

First we segment the different DFR recordings for the same disturbance using abrupt change detection.

ƒ

Then we estimate the individual fault inception timings of the segmented but unsynchronized recordings.

ƒ

We choose the recording with the minimum fault inception time as the reference one. (In this case, it is the DFR-3 recording as evident from Table-1.)

ƒ

We synchronize the rest of the recordings with the reference recording by equating their fault inception times with the reference fault inception time; i.e., we left-shift the rest of the recordings, their fault inception times equated to the reference one.

ƒ

Then we again perform the abrupt change detection based segmentation on these synchronized recordings to have the synchronized, segmented recordings for further analysis.

Application of the synchronization algorithm on the unsynchronized recordings shown in Figure 2 results in the synchronized, segmented recordings as depicted in Figure 3. DFR-3 recording with the minimum fault inception time is chosen as the reference and the other two recordings are synchronized accordingly.

Table 2 Change Time-instants of the synchronized, segmented analog DFR recordings Recordings

Segment A-B Time-instant (Sample No.)

Segment B-C Time-instant (Sample No.)

Segment C-D Time-instant (Sample No.)

DFR-3 DFR-1 DFR-2

770 770 770

946 962 992

3688 3704 3672

RELAY PERFORMANCE MONITORING

The synchronized, segmented analog signals with the matched synchronized binaries can be used to monitor different performance characteristics of the protective relays, e.g., fastest relay operating time, auto-reclosing of the circuit-breakers, main-1 and main-2 relay operation.

Figure 3 Synchronization of three DFR recordings

After synchronizing the analog signals (voltage signals in this case) of the different DFRs, the respective binaries are also synchronized and matched against the synchronized, segmented analog signals. One such example for the DFR-3 recording, analog voltage and binaries for the fault duration and circuit-breaker autoreclosure are shown in Figure 4.

Fastest Relay Operating Time To determine the fastest relay operating time, first we need to determine the fault duration. This can be done by estimating the duration of the segment B (fault) in the synchronized analog plots as shown in Figure 3. Table-3 lists the fault duration times of the three DFR recordings shown in Figure 3 in terms of number of samples and milliseconds. Table 3 Fault Duration of different DFR recordings Recordings

DFR-3 DFR-1 DFR-2

Fault Duration

Fault Duration

(No. of Samples)

(Milliseconds)

946–770 = 176 962–770 = 192 992–770 = 222

70.4 76.8 88.8

For determining the fastest relay operation we need to select the minimum fault duration from the different synchronized DFR recordings. In this case, this is the DFR-3 fault duration (70.4 milliseconds) from the Table-3. The formula for calculating the fastest relay operating time is the following: Fastest Relay Operating Time = Fault Duration – Trip Time

(5)

Figure 4 Synchronized Analog and Binary plots

After this, using the matched binary plots as guard against any possible discrepancies, we estimate the change time-instants of the synchronized, segmented analog recordings of the different DFRs. Table-2 lists the change time-instants of the recordings in Figure 3.

Most of the circuit-breakers in the Eskom transmission system are two cycle breakers [4], i.e., the expected tripping time is in the region of 40 milliseconds (50 Hz system). Using this information, we can compute the fastest relay operating time during the disturbance, which for our example case is 70.4 – 40 = 30.4 milliseconds. The fastest relay operating time gives a fair amount of idea whether the relays are operating correctly or they require maintenance. Auto-Reclosing of the Circuit-Breakers From the synchronized, segmented analog signals and their matched binaries, it is possible to analyze autoreclosing of the circuit-breakers.

By comparing the signal parameter values of the segment A and D in the synchronized analog plots as shown in Figure 3, it can be determined whether the auto-reclosing is successful or not following the relay operation. In this case, matching the segment A and D signal parameters values of the synchronized analog plots in Figure 3 yields that auto-reclosing of the circuitbreakers have been successful. Length of the auto-reclosing can be determined by estimating the duration of the segment C in the synchronized analog plots as shown in Figure 3. Using the synchronized analog plots of Figure 3 and Table-2 values, we can compute the length of auto-reclosing (segment C) for all the three DFR recordings, as listed in Table-4. Table 4 Auto-Reclosing length of DFR recordings Recordings

Auto-Reclosing Length

Auto-Reclosing Length

(No. of Samples)

(Milliseconds)

DFR-3 DFR-1 DFR-2

3688–946 = 2742 3704–962 = 2742 3672–992 = 2680

1096.8 1096.8 1072

Main-1 and Main-2 Relay Operation Every feeder in Eskom transmission system is equipped with two identical relays, main-1 and main-2 with the same settings for distance protection [4]. The idea behind it is to avoid the possibility of fault on the protection side when the incident occurs. Information regarding main-1 and main-2 relay operations can be obtained from the synchronized, matched binaries depending on the distance protection scheme. Analysis of main-1 and main-2 relay operation data gives the idea whether the relays employed for the distance protection are working properly or not.

The relay operating times can be used to obtain relationship between the fault location and the tripping speed. Using that relationship and system impedance ratio, impedance plots for the relays can be drawn, which can be used to analyze the distance protection. Distance protection at Eskom have three zones of protection, each having a certain impedance reach with respect to the impedance of the line; Zone 1 - 80%, Zone 2 - 120% and Zone 3 - 150% of the line impedance [4]. Further discussion of this topic is out of scope of this paper. CONCLUSION

Abrupt change detection using the wavelet transform and threshold method is quite effective in segmenting the signals originated by power system disturbances into event-specific sections. A novel synchronization algorithm for the different simultaneous disturbance recordings, segmented using abrupt change detection, is also discussed in this paper. Using the synchronized and

segmented analog signals and their respective matched binaries, further effective analysis can be done for monitoring the performances of the protective relays, e.g., fastest relay operating time, auto-reclosing of the circuit-breakers, main-1 and main-2 relay operation. The methods and algorithms proposed in this paper facilitate fast and reliable relay performance monitoring along with effective disturbance signal processing for further automatic disturbance recognition and analysis. REFERENCES 1. Craigmile P.F., Percival D.B., “Wavelet-Based Trend Detection and Estimation”, Department of Statistics, Applied Physics Laboratory, University of Washington, Seattle, WA, 2000. 2. Donoho D.L., Johnstone I.M., “Ideal Spatial Adaptation by Wavelet Shrinkage", Biometrika, vol. 81, no. 3, pp. 425-455, 1994. 3. Chantler M., Pogliano P., Aldea A., Tornielli G., Wyatt T., Jolley A., “The Use of Fault-Recorder Data for Diagonising Timing and Other Related Faults in Electricity Transmission Networks”, IEEE Transactions on Power Systems, vol. 15, no. 4, November 2000. 4. Stokes-Waller E., “Automated Digital Fault Recording Analysis on the Eskom Transmission System”, Southern African Conference on Power System Protection, South Africa, 1998. 5. “IEEE Standard Common Format for Transient Data Exchange (COMTRADE) for Power Systems”, IEEE Standard C37.111-1991, Version 1.8, February 1991. 6. Ukil A., Zivanovic R., “Detection of Abrupt Changes in Power System Fault Analysis: A Comparative Study”, Southern African Universities Power Engineering Conference (SAUPEC’05), Johannesburg, South Africa, January 2005. 7. Ukil A., Zivanovic R., “Abrupt Change Detection in Power System Fault Analysis using Wavelet Transform”, International Conference on Power Systems Transients (IPST’05), Montreal, Canada, June 2005 (Accepted). 8. Mallat S., A wavelet tour of signal processing, Academic Press, 1998. 9. Daubechies I., Ten Lectures on Wavelets, Society for Industrial and Applied Mathematics, Philadelphia, 1992.

AUTHOR’S ADDRESS A. Ukil can be contacted at Zethushof 209, Park St. 620, Pretoria, 0083, South Africa. E-mail: [email protected] Tel: +27 (0) 72 736 9557; Fax: +27 12 460 7440 R. Zivanovic can be contacted at P.O. Box 8484, Pretoria, 0001, South Africa. E-mail: [email protected] Tel: +27 12 460 7440; Fax: +27 12 460 7440

application of abrupt change detection in relay ...

the recordings of the digital fault recorders (DFRs) play a significant role in fast ... Model-free approach and Non-parametric approach [6]. Among these ...

181KB Sizes 1 Downloads 245 Views

Recommend Documents

APPLICATION OF ABRUPT CHANGE DETECTION IN ...
Dec 18, 2005 - cost factor because only one PC is needed and the communication network is ..... is the estimate of the parameter vector θ at time t , and )(.

application of abrupt change detection-based signal ...
primary focus on detecting the change time-instant. 0 t , it is useful ... Proceedings of the 15th Southern African Universities Power Engineering Conference. 250 ...

abrupt change detection in automatic disturbance ...
155. 9.6.3. Citrix®. ...... client computing etc) for the ASP implementation are discussed in details. We also discuss the utilisation of the ..... to create the software package for the automatic disturbance recognition and analy- sis. 2.6 Overview

Abrupt Change Detection in Power System Fault ...
Jun 23, 2005 - (FDI) systems; one such domains viz., power systems fault analysis is the .... between zero hertz and half the data sampling frequency. The.

DETECTION OF ABRUPT CHANGES IN POWER ...
Abstract: Detection of abrupt changes in signal characteristics has significant role to play in failure detection and isolation (FDI) systems; one such domains viz., power systems fault analysis is the focus of this paper. Two most promising techniqu

107 - Abrupt climate change, can society cope.pdf
107 - Abrupt climate change, can society cope.pdf. 107 - Abrupt climate change, can society cope.pdf. Open. Extract. Open with. Sign In. Main menu. Displaying ...

A Review on Change Detection Methods in Hyper spectral Image
Keywords: - Change detection, hyper spectral, image analysis, target detection, unsupervised ..... [2] CCRS, Canada Center for Remote Sensing, 2004.

Review Article Digital change detection methods in ...
last may be caused by intrinsic vegetation processes (e.g. succession), land-use ... of change whereby spatial entities either (1) become a different category, (2) .... monitor non-forest to successional shrubs stage, and another five to 10 years to

Multi-Scale Change Point Detection in Multivariate ...
can also be used as a layer of a deep network, in composition with other neural layer types such as convolutional and fully connected layers. For example, the input to a wavelet layer can be the output of a convolutional layer. To apply a convolution

PCA Feature Extraction For Change Detection In ieee.pdf ...
Whoops! There was a problem previewing this document. Retrying... Download. Connect more apps... PCA Feature ... In ieee.pdf. PCA Feature E ... n In ieee.pdf.

unsupervised change detection using ransac
the noise pattern, illumination, and mis-registration error should not be identified ... Fitting data to predefined model is a classical problem with solutions like least ...

Unsupervised Change Detection with Synthetic ...
False alarm rate no SRAD. 0.05%. 0.02%. 0.1. 0.21%. 0.01%. 0.5. 82.30%. 0%. 1.0. 80.05%. 0%. Alessandria. Λ (SRAD). Detection accuracy. False alarm rate.

Abrupt rise in atmospheric CO2 overestimates ... - John Klironomos
Feb 10, 2005 - ability of the AMF community to influence plant biomass. On the ..... the US Department of Energy, and to M.C.R. by the US National Science ...

Multiple Relay Topologies in Cellular Networks
network coding, outage probability ... distributed channel-coding cooperation included in schemes ... who”, meaning that for each RN from the R-node set, we.

Application-Independent Evaluation of Speaker Detection
best any speaker detection system can do is limited by: • The information in ...... AIP Conference ... IEEE Trans. on Speech and Audio Processing, Vol. 9, No.8:.

Abrupt rise in atmospheric CO2 overestimates ...
Feb 10, 2005 - a heavy carbon drain. Per cent root colonization by ..... floor. Smaller workers of C. atratus, and smaller species of. Cephalotes more generally ...

Multiple Relay Topologies in Cellular Networks
cooperative wireless networks [5] in order to increase the diversity gain. For the multiple-source multiple-relay (MSMR) topologies, the graph representation of ...

subminiature dip relay - GitHub
Bounce time ... 2) In case 5V of transistor drive circuit, it is recommended to use .... with the consideration of shock risen from transit and relay mounting, it should.

image change detection on urban area: the earthquake ...
a DISTART, University of Bologna, Viale Risorgimento, 2, 40136 Bologna, Italy - ... be used in loci to help post survey damage assessment and macroseismic evaluation, but in the ..... meaningful regions, to simulate the abstraction done by a.

Adaptive Sequential Bayesian Change Point Detection
Dec 12, 2009 - The underlying predictive model (UPM) p(xt|x(t−τ):t−1 =: x. (τ) t. ,θm) for any τ ∈ [1,..., (t − 1)], at time t. The hazard function H(r|θh).

A New Shot Change Detection Method Using ...
Department of Electronic Engineering, Shanghai Jiao Tong University ..... Consumer Electronics, vol. 49, pp. ... Circuits and Systems for Video Technology, vol.