An Improved Control Law Using HVDC Systems for Frequency Control Jing Dai

Gilney Damm

Department of Energy, SUPELEC 3 rue Joliot-Curie, 91192 Gif-sur-Yvette, France [email protected]

Laboratoire IBISC, Universit´e d’Evry-Val d’Essonne 40 rue du Pelvoux, 91020 Evry, France [email protected]

Abstract—We consider coordination of primary frequency control efforts among non-synchronous AC areas connected by a multi-terminal HVDC grid. we propose an improve version of a control law that modifies the DC voltages of the HVDC converters in order to share the primary reserves between the AC areas. Compared to the original control law, the improved one is able to eliminate the differences between the AC areas’ frequencies in steady state, which results in a higher degree of reserve sharing. A theoretical study proved the stability of the linearized closed-loop system, and simulation results on the nonlinear system demonstrate the effectiveness of the control law. Index Terms—Frequency control, HVDC.

I. I NTRODUCTION High voltage direct current (HVDC) transmission systems have been used for some decades now. They present several advantages over alternative current (AC) systems in some situations. In particular, they are very interesting for long distance transmission, as well as for connecting offshore wind farms. Despite its long-time application for point-to-point transmission, the problem of multi-terminal HVDC is widely open. Traditionally, among all the converters of a multi-terminal HVDC system, only one keeps the power balance of the DC grid by regulating its DC voltage, while all the others transfer a pre-scheduled amount of power. This operation mode is very simple to implement, and can prevent cascade outages. However, it also has some drawbacks: (i) the AC zone connected by the converter regulating the DC voltage must be strong enough to counteract the disturbance resulting from the disconnection of other zones. This is especially pronounced in the case of a multi-terminal HVDC system that connects several zones of relatively similar sizes; (ii) the primary frequency control reserves are not shared among the zones, i.e. when one zone suffers from a power imbalance resulting in a frequency excursion, other zones would not respond to help rebuild its power balance, as is the case of an AC interconnection. To address the first disadvantage, some works (e.g. [2]) suggested to use more than one converter to regulate the DC voltage. For the second drawback, some articles (e.g. [1], [4],

[5], [6], [7], [8]) proposed control laws aiming at sharing primary reserves among the zones. Most of these control laws change the power transferred through the converters, based on remote frequency information, where the delays associated with the indispensable communication between remote zones may jeopardize stability [3]. In order to be relieved from this dependence on remote information, [4] proposed a control scheme where each converter controls its DC voltage such that the DC voltage deviation is proportional to the local frequency deviation. The control of the DC voltage at each converter implicitly addresses the first drawback. Furthermore, the use of local information gives the control scheme the advantage of being decentralized. However, as no communication between the zones is involved, the frequency deviations of the areas would remain different in steady state in the aftermath of a power imbalance. It is true that such differences can be made smaller by increasing the controller gain, but a large controller gain would also jeopardize system stability. Moreover, these steady-state differences also imply a smaller degree of reserves sharing than the case of an AC interconnection. This article proposes an improved version of the control law proposed in [4]. By including an integral term of the local frequency deviation, the new control scheme is able to eliminate the differences between the zones’ frequency deviations. However, as the integral term has a cumulative effect on the DC voltage, we hierarchically couple the controller with another term that brings back communication between the converters, which aims at preventing the DC voltage from drifting away from its nominal value. The hierarchical structure allows on the other hand the required communication to be made in another time scale such that the remote information can be updated at a slower rate without compromising the control law’s effectiveness in terms of reserve sharing. The rest of the paper is organized as follows. Section II models the HVDC system and defines a reference operating point. Section III elaborates on the new control law and theoretically proves its stability. Section IV gives simulation results and discusses the practical implementation of the control law. Section V concludes.

two points in the DC grid. Each converter is considered to be capable of instantaneously applying a control input in the form of either the power injection Pidc or the DC voltage Vidc . In other words, either Pidc or Vidc can be used as the control variable.

DC grid

Converter 1

Converter N Converter 2

AC area 1

AC area N

B. Reference operating point

AC area 2

Fig. 1. A multi-terminal HVDC system connecting N AC areas via N converters.

II. M ULTI - TERMINAL HVDC SYSTEM MODEL AND REFERENCE OPERATING POINT

A. System model The multi-terminal HVDC system model considered in this paper is composed of a DC grid, N separate AC areas, and N converters that interface the AC areas with the DC grid, as shown in Fig. 1.

The reference operating point of the system is a steady state at which the system is supposed to rest prior to any disturbance. It is defined by specific values of the input o ) and the variables (fi , Pmi , Pli , Pidc , parameters (Plio , Pmi Vidc ). We denote values at the reference operating point by the corresponding symbols with a bar overhead. At the reference operating point, for i = 1, 2, ..., N , f¯i = fnom,i . Then (3) directly yields P¯li = P¯lio , and o imposing equilibrium in (2) yields P¯mi = P¯mi and in dc o o ¯ ¯ ¯ (1) yields Pi = Pmi − Pli . (4) provides a final set of equations PNlinking the voltage values to the other variables P¯idc = k=1 V¯idc (V¯idc − V¯kdc )/Rik .

The dynamics of each AC area are modeled as dfi Pmi − Pli − Pidc = − 2πDgi (fi − fnom,i ) , (1) dt 2πfi Pnom,i fi − fnom,i dPmi o =Pmi − Pmi − , (2) Tsmi dt σi fnom,i Pli =Plio · (1 + Dli (fi − fnom,i )) , (3)

III. C ONTROL LAW

2πJi

where the state variables are fi , the frequency of area i, and Pmi , the mechanical power input in the areas. Other variables in the above equations are Pli , the aggregated load of area i, and Pidc , the power injected from area i into the DC grid. The parameters are: fnom,i the nominal frequency, Plio the aggregated load of area i at the nominal frequency, Dli frequency sensitivity factor of the aggregated load, Ji the moment of inertia of the aggregated generator of area i, Dgi the damping factor of the generator, σ the generator droop, Pnom the rated mechanical power of the generator, o the reference value of Pmi at the nominal frequency, Pm and Tsm the time constant associated with the dynamics of primary frequency control. Briefly speaking, (1) describes how the frequency varies as a result of the power balance within area i, (2) characterizes primary frequency control that adjusts the generator’s mechanical power in response to frequency excursions, and (3) shows the frequency-dependent nature of the load. Detailed physical interpretation of the above equations can be found in [5]. The DC grid interconnects the AC areas via the converters. By Ohm’s law, the power Pidc satisfies Pidc

=

N X V dc (V dc − V dc ) i

k=1

i

Rik

k

,

(4)

where Vidc and Vkdc are the DC voltages of converters i and k respectively and Rik is the effective resistance between these

A. Original control law The original control law proposed in [4] is ∆Vidc = α∆fi ,

(5)

where ∆Vidc = Vidc − V¯idc and ∆fi = fi − f¯i . In response to a power imbalance in one area, this control law makes the ∆fi close to each other, but the differences between them can not be eliminated, which leads to a smaller degree of primary frequency control reserve sharing than the case with the control law studied in [3], [5] that results in an identical ∆fi in all zones. B. Improved control law To eliminate the differences between ∆fi in steady state, we propose the following improved control law: ∆Vidc = α∆fi + β

Z ∆fi dt − γ

Z X N

∆Vkdc dt .

(6)

k=1

Compared to (5), the new control law includes two additional terms. The integral term of ∆fi is used to nullify the differences between fi , while the integral term of the sum of ∆Vidc of all the zones aims at preventing the continual drifting of Vidc . In fact, if γ = 0, then, even when all ∆fi have already converged to a (common) steady-state value, ∆Vidc would still keep drifting away as long as ∆fi 6= 0. On a larger time scale, when fi is restored to fnom thanks to the secondary frequency control, the new steady-state value of Vidc would be different

dv dx =α + βx − γ1TN v1N , dt dt u = (C¯ + V¯ L)v ,

from its value prior to the disturbance1 , implying a continual change of working point of the converters as power imbalances occur in the areas. The introduction of the γ term in (6) makes the control law no longer decentralized. However, as will be shown in Section IV-C, the communication does not have to be instantaneous, and the γ term be updated at a slower rate without compromising the control law’s effectiveness.

2πJi

Pmi − Plio − Pidc dfi = − 2πDi (fi − fnom,i ) , dt 2πfi

(7)

where Di = Dgi + P¯lio Dli /(4π 2 fnom,i ). The DC load flow (4) is linearized as ∆Pidc

P¯ dc = ¯idc ∆Vidc + Vi

N X k=1

V¯idc (∆Vidc − ∆Vkdc ) . Rik

(8)

Proposition 1: Consider the linearized system modeled by (2), (7), (8) under the control law (6). Then at the equilibrium point associated to load imbalances, the frequency deviations of all areas are equal. Proof: Differentiating (6) and taking time derivatives of the variables equal to zero yield γX ∆Vkdc . (9) ∆fi = β k

As the expression of ∆fi is independent of the area index i, the frequency deviations of all areas are identical.  Proposition 2: Consider the closed-loop system modeled by (2), (6), (7), (8). Then at the equilibrium point associated to load imbalances, the system is stable and converges to its equilibrium point. Proof: Let xi = ∆fi , yi = Pmi − P¯mi , ui = Pidc − P¯idc , vi = ∆Vidc , di = Plio − P¯lio . Define the vectors x = [x1 , x2 , . . . , xN ]T , y = [y1 , y2 , . . . , yN ]T , u = [u1 , u2 , . . . , uN ]T , v = [v1 , v2 , . . . , vN ]T , d = [d1 , d2 , . . . , dN ]T . Then, (2), (6), (7), (8) can be written in matrix form representing the entire interconnected system as dx = −A1 x + A2 y − A2 u − A2 d , dt dy = −A3 x − A4 y , dt

(10) (11)

1 It is true that positive and negative power imbalances may happen to cancel each other’s cumulative effects on the drifting of Vidc . However, in the general case, either positive or negative imbalances dominate and their cumulative effects in the long term would make the converters’ DC voltage drift to an unacceptably high or low value.

(13)

where A1 = diag{Di /Ji }, A2 = diag{1/(4π 2 fnom,i Ji )}, A3 = diag{Pnom,i /(Tsmi σi fnom,i )}, A4 = diag{1/Tsmi }, C¯ = diag{P¯idc /V¯idc }, V¯ = diag{V¯idc }, and 1N is the column vector of length N with all elements equal to 1. Replacing dx/dt in (12) by (10) yields dv =(−αA1 + βIN )x + αA2 y dt − αA2 u − αA2 d − γ1TN v1N ,

C. Theoretical study In this part, we study the stability property of the closedloop system linearized around the reference operating point as follows. Equation (1) is linearized with (3) taken into consideration as

(12)

(14)

where IN is the identity matrix of dimension N and we used the fact that 1TN v1N = 1N 1TN v . By eliminating u, we can write the closed-loop system as       A2 x x d   y = S y −  0  d , (15) dt v v αA2 where 

−A1 −A3 S= −αA1 + βI

A2 −A4 αA2

 −A2 (C¯ + V¯ L)  . 0 T ¯ ¯ −αA2 (C + V L) − γ1N 1N

Through some rank-preserving transformations, it can be shown that S has full rank. Thus, the steady-state values of x, y and v are unique and are given by     A2 xss yss  = S −1  0  d . (16) αA2 vss In the following, we prove by contradiction that all the eigenvalues of S must have negative real part. Denote by 0. Let (q1 , q2 , q3 )T be its corresponding eigenvector, then we can find (C¯ + V¯ L)q3 = − A∗ q1 , (λIN + where ∗

A =



γ1N 1TN )q3

(17)

=(αλ + β)q1 ,

A1 + λIN A3 + A2 A4 + λIN

(18)

 .

Since the matrix 1N 1TN is positive definite2 , (18) yields q3 = (λIN + γ1N 1TN )−1 (αλ + β)q1 .

(19)

Together with (17), we have (C¯ + V¯ L)(λIN + γ1N 1TN )−1 (αλ + β) = −A∗ .

(20)

From its definition, the matrix C¯ has at least one eigenvalue with positive real part, so does the left side of (20). However, 2 Note

that T T T 2 xT 1N 1T N x = (x 1N )(1N x) = (1N x) .

1 50

3

4

frequency (Hz)

5

2

49.99 49.98 49.97 1 2 3 4 5

49.96 49.95

Fig. 2.

Topology of the DC grid.

49.94 TABLE I

49.93 0

PARAMETERS AND INITIAL VALUES FOR THE AC AREAS . AC area 1 2 3 4 5 Unit Pnom 50 80 50 30 80.4 MW J 2026 6485 6078 2432 4863 kg m2 Dg 48.4 146.4 140 54.7 95.1 W s2 σ 0.02 0.04 0.06 0.04 0.03 / Tsm 1.5 2.0 2.5 2 1.8 s o Pl 100 60 40 50 40 MW P¯ dc -50 20 10 -20 40.4 MW V¯ dc 99.17 99.60 99.73 99.59 100 kV o fnom,i = 50Hz, Dli = 0.01s, and Pm,i = Pnom,i for all i.

Fig. 3.

10

15 time (s)

20

25

30

fi under the original control law (5).

50 frequency (Hz)

the matrix A∗ is positive definite, which leads to a contradiction. Therefore, such a λ with positive real part cannot exist, and the closed-loop system is thus stable and converges to the unique equilibrium point given by (16) following a power imbalance. 

5

49.99 49.98 1 2 3 4 5

49.97 49.96 49.95 49.94

IV. S IMULATION RESULTS AND PRACTICAL IMPLEMENTATION

49.93 0

5

10

15 time (s)

20

25

30

A. Simulated system To empirically test the new control law, we run simulations on the same system as used in [3], [4], [5]. The system is composed of five AC areas, interconnected by a DC grid whose topology is shown in Fig. 2. The parameters of the AC areas are shown in Table I, and the resistances of the DC grid are: R12 = 1.39Ω, R15 = 4.17Ω, R23 = 2.78Ω, R25 = 6.95Ω, R34 = 2.78Ω and R45 = 2.78Ω. The full non-linear system model (1), (2), (3), (4) is simulated using an Euler method with a time-discretisation step of 1ms. The load disturbance o considered is a step increase by 5% of Pl2 . The controller gains are chosen as α = β = 1000 and γ = 0.1. B. Simulation results The frequencies of the AC areas under the original control law (5) and the new one (6) are shown respectively in Figs. 3 and 4. These figures show that the new control law indeed eliminates the steady-state differences between the frequency deviations. The control variables (V dc ) under the new control law with γ = 0.1 and γ = 0 are shown respectively in Figs.

Fig. 4.

fi under the new control law (6).

5 and 6, which demonstrate the role of the γ term to prevent the continuous drifting of Vidc . C. Practical implementation The introduction of the γ term necessitates communication between the HVDC terminals. To take into account the delay, the γ term are updated only every 500 ms. Simulation results show that the less frequent update of the γ term seems to have little impact on fi , while the curves of Vidc become serrated, as shown in Fig. 7, which would pose no problem to the operation of HVDC converters. V. C ONCLUSIONS This paper proposed an improve version of a control law originally proposed in [4] that modifies the DC voltages of the HVDC converters in order to share the primary frequency

V (kV)

100

V5

99.8

V3

99.6

V4

99.4

V2

99.2

V1

99 0

Fig. 5.

control reserves between the AC areas connected by the HVDC grid. Compared to the original control law, the new one is able to eliminate the differences between the AC areas’ frequencies in steady state, which results in a higher degree of reserve sharing. A theoretical study proved the stability of the linearized system under the new control law, and simulation results on the non-linear system demonstrate its effectiveness.

5

Vidc

10

15 time (s)

ACKNOWLEDGMENTS

20

25

30

The first author is thankful to the financial support from the Laboratoire des Signaux et Systemes (L2S), CNRS SUPELEC - Univ Paris-Sud where he carried out the work on this paper.

under the new control law (6) with γ = 0.1.

R EFERENCES

V (kV)

100 99.8

V5

99.6

V3

99.4

V4

99.2

V2

99

V1

98.8 98.6 0

Fig. 6.

5

10

15 time (s)

20

25

30

Vidc under the new control law (6) with γ = 0.

100

V (kV)

V5 99.8

V3

99.6

V4

99.4

V2

99.2

V1

99 0

The authors are grateful to the comments and suggestions by Yannick Phulpin from EDF R&D, Damien Ernst from the University of Li`ege, and Yijing Chen from the Laboratoire des Signaux et Systemes (L2S), CNRS - SUPELEC - Univ Paris-Sud.

5

10

15 time (s)

20

25

30

Fig. 7. Vidc under the new control law (6) when the γ term is updated every 500ms.

[1] B. H. Bakken and H. H. Faanes. Technical and economic aspects of using a long submarine HVDC connection for frequency control. IEEE Transactions on Power Systems, 12(3):1252–1258, August 1997. [2] J. Beerten, D. Van Hertem, and R. Belmans. VSC MTDC systems with a distributed DC voltage control - A power flow approach. In Proceedings of IEEE Trondheim PowerTech, Trondheim, Norway, June 2011. [3] J. Dai, Y. Phulpin, A. Sarlette, and D. Ernst. Impact of delays on a consensus-based primary frequency control scheme for AC systems connected by a multi-terminal HVDC grid. In Proceedings of the IREP Symposium - Bulk Power Systems Dynamics and Control - VIII, Buzios, Rio de Janeiro, Brazil, August 2010. [4] J. Dai, Y. Phulpin, A. Sarlette, and D. Ernst. Voltage control in an HVDC system to share primary frequency reserves between non-synchronous areas. In Proceedings of the 17th Power Systems Computation Conference (PSCC), Stockholm, Sweden, August 2011. [5] J. Dai, Y. Phulpin, A. Sarlette, and D. Ernst. Coordinated primary frequency control among non-synchronous systems connected by a multiterminal high-voltage direct current grid. IET Generation, Transmission & Distribution, 6(2):99–108, February 2012. [6] T. M. Haileselassie, R. E. Torres-Olguin, T. K. Vrana, K. Uhlen, and T. Undeland. Main grid frequency support strategy for VSC-HVDC connected wind farms with variable speed wind turbines. In Proceedings of IEEE Trondheim PowerTech, Trondheim, Norway, June 2011. [7] M. Sanpei, A. Kakehi, and H. Takeda. Application of multi-variable control for automatic frequency controller of HVDC transmission system. IEEE Transactions on Power Delivery, 9(2):1063–1068, April 1994. [8] A. Sarlette, J. Dai, Y. Phulpin, and D. Ernst. Cooperative frequency control with a multi-terminal high-voltage DC network. Automatica, 48(12):3128–3134, December 2012.

An Improved Control Law Using HVDC Systems for ...

distance transmission, as well as for connecting offshore wind farms. Despite its ... HVDC system, only one keeps the power balance of the. DC grid by ..... cumulative effects in the long term would make the converters' DC voltage drift to an ...

267KB Sizes 0 Downloads 306 Views

Recommend Documents

An Improved Control Law Using HVDC Systems for ...
Aug 28, 2013 - Systems for Frequency Control. Jing Dai1. Gilney Damm2 ... information. ... This lead to a smaller degree of primary reserve sharing, than the ...

Improved H∞ Control for Discrete-Time Polytopic Systems
Keywords—H∞ control, Polytopic systems, Robust perfor- .... matrices are given by. [A(α) B(α) Bu(α). C(α) D(α) Du(α)]. = N. ∑ i=1 αi [Ai. Bi. Bui. Ci. Di. Dui]. (6).

An improved memetic algorithm using ring neighborhood ... - GitHub
4, 5, 6, 7 that the con- vergence to the known optimal result of test functions is very fast and most test functions have been converged after around. 1 × 105 FEs.

An improved memetic algorithm using ring neighborhood ... - GitHub
Nov 29, 2013 - The main motivation of using ring neighborhood topology is to provide a good ... mine the choice of solutions for local refinements, by utiliz- ...... 93,403 g08. 2,755. 2,990 g09. 13,455. 23,990 g10. 95,788. 182,112 g11. 1,862.

An Improved LEACH Protocol by Using Two Suitability Functions
consumption and increases the lifetime of associated nodes. In next stage, for election cluster member, using one other suitability function. Simulation is conducted in using MATLAB results are analyzed for energy consumption. Keywords: LEACH, Node,

An Improved LEACH Protocol by Using Two Suitability Functions
describes the wireless sensor network model, Section 4 describes radio energy model, Section 5 explains .... Radio Energy Model. We use the same radio model as stated in [5, 13]. Matching to the radio energy dissipation model of Fig. 1, the energy co

improved rate control and motion estimation for h.264 ... - CiteSeerX
speed in designing the encoder. The encoder developed by the Joint ..... [3] “x264,” http://developers.videolan.org/x264.html. [4] “MPEG-4 AVC/H.264 video ...

Identification and Control of Nonlinear Systems Using ...
parsimonious modeling and model-based control of nonlinear systems. 1. ...... In this example, the flow rate is constant ... A schematic diagram of the process. Vh.

An Improved Degree Based Condition for Hamiltonian ...
Lenin Mehedy1, Md. Kamrul Hasan1 and Mohammad Kaykobad2. 1Department of Computer Engineering, Kyung Hee University, South Korea. 2Department of Computer Science and Engineering, North South University, Dhaka, Bangladesh. Email: 1{lenin, kamrul}@oslab

An Improved Divide-and-Conquer Algorithm for Finding ...
Zhao et al. [24] proved that the approximation ratio is. 2 − 3/k for an odd k and 2 − (3k − 4)/(k2 − k) for an even k, if we compute a k-way cut of the graph by iteratively finding and deleting minimum 3-way cuts in the graph. Xiao et al. [23