Equipment Portal

Automated Logic’s Equipment Portal (EQ-PRTL) sets a new standard for integrating other manufacturers’ equipment into WebCTRL®. EQ-PRTL is a powerful gateway to a single piece of equipment /device using proprietary or open protocols such as Modbus and LonWorks. Support for BACnet® over ARCNET 156 kbps and MS/TP communications are standard. Key Features and Benefits • Serves as an economical field gateway to a single piece of equipment/device utilizing an open or proprietary protocol. (Note: Maximum of 100 integration points per EQ-PRTL.) • Optional Lon Plug-in Card eliminates need for Lon SLTA when integrating to Lon devices. • Graphically programmable via EIKON®, EQ-PRTL is able to execute complex integration control strategies at the field level. • Built-in support for Automated Logic’s line of backlit LCD display/keypad (BACview) provides the option of installing a local user interface for monitoring and control. • Built-in support for Automated Logic’s line of RS room sensors provides the flexibility of remote room temperature sensing. • Battery backed real-time clock ensures full continuity of operation in the event of power failures and communications failures. • Non-volatile, battery-backed RAM stores application programs, trends, and other data if power is lost. • Flash memory makes for easy field upgrades over network. • 16 bit microprocessor combined with ARCNET 156 kbps 1150 Roberts Boulevard communications offers ample horsepower and speed for equipment Kennesaw, Georgia 30144 integration requirements. 770/429-3000 Fax 770/429-3001 www.automatedlogic.com

Equipment Portal Specifications Enterprise System

Web Browser

Cell Phone

Web Browser

PDA Server

XML/SOAP

HTML/HTTP

WML/WAP

WML/WAP

BACnet®/IP, 100Base-T Ethernet

HTML/HTTP

Internet

To Third Party Equipment Ethernet, ARCNET, EIA-485, EIA-232

ME812u-E Controller

LGR Router or ME-LGR Router/Controller

BACnet MS/TP, ARCNET To Third Party Equipment EIA-485, EIA-233

ME line Controller

SE line Controller

ZN line Controller Room Controller

Room Sensor

Room Sensor

Room Sensor

BACnet Support:

Conforms to the BACnet Application Controller (B-AAC) Standard Device as defined in BACnet 135-2001 Annex L.

Communication:

The following ports are available: - BMS Port: EIA-485 port jumper configurable as ARCNET 156 kbps or MS/TP (9600 bps – 78.6 kbps) - Equipment Port: EIA-232/EIA-485 software configurable - Optional Lon Port for using LonWorks communications plug-in device - Local Computer Access Port for startup and troubleshooting - R-net Port for support of RS Sensors and BACview local interface

Microprocessor:

High speed 16 bit microprocessor with one ARCNET communication co-processor.

Memory:

1M Byte non-volatile battery backed RAM, 1M Byte flash memory, 16 bit memory bus. (Shelf life of battery is 10 years with 10,000 hours of continuous operation).

Real-time Clock:

Battery-backed real-time clock.

Status Indicators:

Visual (LED) status of power, network communication, running, and errors.

Module Addressing:

Rotary dip switches.

Protection:

Built-in surge and transient protection circuitry - internal solid state resettable fuses on the incoming power and network connections.

Listings:

FCC, UL, cUL, and CE.

Environmental Operating Range:

-22° to 150°F (-30° to 65.5°C); 10 to 95% relative humidity, non-condensing.

Power Requirements:

24V-ac ± 15% (20.4V-ac to 27.6V-ac), 50 to 60Hz, 10VA power consumption (single Class 2 source only, 20VA or less)

Physical:

Rugged GE C2950 Cycoloy plastic.

Weight:

9 oz.

Dimensions:

4” (width) by 5” (height) by 1.75” (LON option card mounts in a separate 3.5” x 3.25” snap track). 102mm (width) by 127mm (height) by 45.5mm (recommended panel depth, add 19mm for the option card).

Mounting:

2” (width) by 4.8” (height) 51mm (width) by 122 mm (height).

Automated Logic Corporation . 1150 Roberts Boulevard . Kennesaw, Georgia 30144 . 770/429-3000 . Fax 770/429-3001 . www.automatedlogic.com © 2008, Automated Logic Corporation. Automated Logic, the Automated Logic logo, EIKON, BACview and WebCTRL are registered trademarks of Automated Logic Corporation. BACnet is a registered trademark of ASHRAE. All other trademarks are the property of their respective owners. Specifications are subject to change without prior notice.

CSEQPRTL

ALC EQ-PRTL.pdf

BMS Port: EIA-485 port jumper configurable as ARCNET 156 kbps or MS/TP. (9600 bps – 78.6 kbps). - Equipment Port: EIA-232/EIA-485 software configurable.

2MB Sizes 13 Downloads 262 Views

Recommend Documents

ALC RC642D.pdf
Battery: 7 year Lithium BR325 battery provides minimum 10,000 hours of data retention during. power outage. Status Indicators: LED status indicators for ...

PPR-ALC-precis.pdf
There are laws of rationality that govern our degrees of belief, our levels of confidence,. our credences. They describe features that our credences must have if ...

2017 Met ALC - new .pdf
PASTA. Page 1 of 1. 2017 Met ALC - new .pdf. 2017 Met ALC - new .pdf. Open. Extract. Open with. Sign In. Main menu. Displaying 2017 Met ALC - new .pdf.